B.8 L: Protection Function

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,

frequency detection, fault restarts, overtorque detection, and other types of hardware protection.

u

L1: Motor Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L1-01

(0480)

Motor Overload

Protection Selection

Mtr OL Charact

0: OL1 Disabled

1: VT Motor

2: CT Motor

3: Vector Motor

4: PM Motor

5: Constant Torque

6: 50Hz VT Motor

0: Disabled

1: General purpose motor (standard fan cooled)

2: Drive dedicated motor with a speed range of 1:10

3: Vector motor with a speed range of 1:100

4: PM motor with variable torque

5: PM motor with constant torque control

6: General purpose motor (50 Hz)

The drive may not be able to provide protection when using

multiple motors, even if overload is enabled in L1-01. Set

L1-01 to 0 and install separate thermal relays to each motor.

Default:

<1>

Range: 0 to 6

L1-02

(0481)

Motor Overload

Protection Time

MOL Time Const

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min

Min.: 0.1

Max.: 5.0

L1-03

(0482)

Motor Overheat Alarm

Operation Selection

(PTC input)

Mtr OH Alarm Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm only

Sets operation when the motor temperature analog input

(H3-02, H3-10, or H3-06 = E) exceeds the oH3 alarm level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

3: Alarm only (“oH3” will flash)

Default: 3

Range: 0 to 3

L1-04

(0483)

Motor Overheat Fault

Operation Selection

(PTC input)

Mtr OH Fault Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

Sets stopping method when the motor temperature analog input

(H3-02, H3-10, or H3-06 = E) exceeds the oH4 fault level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

Default: 1

Range: 0 to 2

L1-05

(0484)

Motor Temperature

Input Filter Time (PTC

input)

Mtr Temp Filter

Adjusts the filter for the motor temperature analog input

(H3-02, H3-10, or H3-06 = E).

Default: 0.20 s

Min.: 0.00

Max.: 10.00

L1-08

(1103)

<2>

oL1 Current Level

OL1 current lvl1

Sets the reference current for motor thermal overload detection

for motor 1 in amperes.

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 0.0 A

Min.: 10% of

drive rated

current

Max.: 150% of

drive rated
current

<3>

L1-09

(1104)

<2>

oL1 Current Level for

Motor 2

OL1 current lvl2

Sets the reference current for motor thermal overload detection

for motor 2 in amperes.

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 0.0 A

Min.: 10% of

drive rated

current

Max.: 150% of

drive rated
current

<3>

L1-13

(046D)

Continuous

Electrothermal

Operation Selection

Mtr OL Mem Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

L1-15

(0440)

Motor 1 Thermistor

Selection (NTC)

M1 OH5 Fault Sel

0: Disabled

1: Enabled

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 0

Range: 0, 1

L1-16

(0441)

Motor 1 Overheat

Temperature

M1 OH5 level

Sets the temperature for motor 1 that triggers an overheat fault

(oH5).

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 120 °C

Min.: 50

Max.: 200