No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-06
(0437)
Watt Hour Output Unit
Selection
Pwr Mon Unit Sel
Sets the output units for the watt hours when Watt Hour Pulse
Output is selected as the digital output (H2-01, H2-02, or H2-03
= 39).
Outputs a 200 ms pulse signal when the watt hour counter
increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 0
Range: 0 to 4
–
H2-07
(0B3A)
<1>
MEMOBUS Register 1
Address Select
MFDO Regs1 Addr
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 62 and 162.
Note:
This parameter is not available in models
4A0930 and 4A1200.
Default: 1
Range: 1 to 1FFF
–
H2-08
(0B3B)
<1>
MEMOBUS Register 1
Bit Select
MFDO Regs1 Bit
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 62 and 162.
Note:
This parameter is not available in models
4A0930 and 4A1200.
Default: 0
Range: 0 to FFFF
–
H2-09
(0B3C)
<1>
MEMOBUS Register 2
Address Select
MFDO Regs2 Addr
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 63 and 163.
Note:
This parameter is not available in models
4A0930 and 4A1200.
Default: 1
Range: 1 to 1FFF
–
H2-10
(0B3D)
<1>
MEMOBUS Register 2
Bit Select
MFDO Regs2 Bit
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 63 and 163.
Note:
This parameter is not available in models
4A0930 and 4A1200.
Default: 0
Range: 0 to FFFF
–
<1> Available in drive software versions PRG: 1019 and later.
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function
LCD Display
Description
Page
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
–
1
Zero speed
Zero Speed
Open: Output speed is greater than the value of E1-09 (Minimum Output
Frequency) or b2-01 (DC Injection Braking Start Frequency).
Closed: Output frequency is less than or equal to the value of E1-09 (Minimum
Output Frequency) or b2-01 (DC Injection Braking Start Frequency).
–
2
Speed agree 1
Fref/Fout Agree1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
3
User-set speed agree 1
Fref/Set Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
4
Frequency detection 1
Freq Detect 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
–
5
Frequency detection 2
Freq Detect 2
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
–
6
Drive ready
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
–
7
DC bus undervoltage
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
–
8
During baseblock
(N.O.)
BaseBlk 1
Closed: Drive has entered the baseblock state (no output voltage).
–
9
Frequency reference
source
Ref Source
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
b1-15).
Closed: Digital operator supplies the frequency reference.
–
A
Run command source
Run Cmd Source
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
–
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
Closed: An overtorque or undertorque situation has been detected.
–
C
Frequency reference
loss
Loss of Ref
Closed: Analog frequency reference has been lost.
Frequency reference loss is detected when the frequency reference drops below
10% of the reference within 400 ms.
–
D
Braking resistor fault
DB Overheat
Closed: Braking resistor or transistor is overheated or faulted out.
Note:
This setting is not available in models 4A0930 and 4A1200.
–
B.7 H Parameters: Multi-Function Terminals
306