Yaskawa CIMR-AU 200V Drives User Manual
Page 251

u
Three-Phase 200 V Class Drive Models 2A0250 to 2A0415
Table A.4 Power Ratings Continued (Three-Phase 200 V Class)
Item
Specification
Drive Models
2A0250
2A0312
2A0360
2A0415
Maximum Applicable Motor Capacity (HP)
<1>
ND Rating
100
125
150
175
HD Rating
75
100
125
150
Input
Input Current (A)
<2>
ND Rating
271
324
394
471
HD Rating
200
271
324
394
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
<3>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
124
148
180
215
HD Rating
91
124
148
180
Output
Rated Output Capacity (kVA)
<4>
ND Rating
<5>
95
119
137
158
HD Rating
82
<6>
108
<6>
132
<6>
158
<5>
Rated Output Current (A)
ND Rating
<5>
250
312
360
415
HD Rating
215
<6>
283
<6>
346
<6>
415
<5>
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User adjustable between 1 and 10 kHz
Maximum Output Voltage (V)
Three-phase 200 to 240 Vac (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC input is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
A.2 Power Ratings
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
251
A
Specifications