Yaskawa CIMR-AU 200V Drives User Manual
Page 362

Drive Model
A1000 in Normal Duty Mode (C6-01 = 1)
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating
Amps
<3>
Bussman Semi-
conductor Fuse
Rating (Fuse
Ampere)
<4>
5A0017
15
23
40
40
60
FWP-100B (100)
5A0022
20
31
60
50
90
FWP-100B (100)
5A0027
25
38
75
60
110
FWP-125A (125)
5A0032
30
45
75
75
125
FWP-125A (125)
5A0041
40
44
75
75
125
FWP-175A (175)
5A0052
50
54
100
90
150
FWP-175A (175)
5A0062
60
66
125
110
175
FWP-250A (250)
5A0077
75
80
150
125
225
FWP-250A (250)
5A0099
100
108
175
175
300
FWP-250A (250)
5A0125
125
129
225
225
350
FWP-350A (350)
5A0145
150
158
300
275
450
FWP-350A (350)
5A0192
200
228
400
350
600
FWP-600A (600)
5A0242
250
263
500
450
700
FWP-600A (600)
<1> Maximum MCCB Rating is 15 A, or 200 % of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussman FWH and FWP are required for UL compliance. Select FWH for 200 V Class and 400 V Class models
and FWP fuses for 600 V models.
<5> Class L fuse is also approved for this rating.
Table C.8 Factory Recommended A1000 AC Drive Branch Circuit Protection (Heavy Duty)
Drive Model
A1000 in Heavy Duty Mode (C6-01 = 0)
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating
Amps
<3>
Bussman Semi-
conductor Fuse
Rating (Fuse
Ampere)
<4>
200 V Class
2A0004
0.75
2.9
15
5
8
FWH-70B (70)
2A0006
1
5.8
15
10
15
FWH-70B (70)
2A0008
2
7
15
12
17.5
FWH-70B (70)
2A0010
2
7.5
15
12
20
FWH-70B (70)
2A0012
3
11
20
17.5
30
FWH-70B (70)
2A0018
3
15.6
25
25
40
FWH-90B (90)
2A0021
5
18.9
35
30
50
FWH-90B (90)
2A0030
7.5
28
50
40
75
FWH-100B (100)
2A0040
10
37
60
60
100
FWH-200B (200)
2A0056
15
52
100
90
150
FWH-200B (200)
2A0069
20
68
125
110
200
FWH-200B (200)
2A0081
25
80
150
125
225
FWH-300A (300)
2A0110
30
82
150
125
225
FWH-300A (300)
2A0138
40
111
200
175
250
FWH-350A (350)
2A0169
50
136
250
225
350
FWH-400A (400)
2A0211
60
164
300
250
450
FWH-400A (400)
2A0250
75
200
400
350
600
FWH-600A (600)
2A0312
100
271
500
450
800
FWH-700A (700)
2A0360
125
324
600
500
900
<4>
FWH-800A (800)
2A0415
150
394
700
600
1100
<4>
FWH-1000A (1000)
C.2 UL and CSA Standards
362