Grounding, Ce standards compliance for dc power supply input, C.1 european standards – Yaskawa CIMR-AU 200V Drives User Manual
Page 348

Drive Model
Fuse Type
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
5A0062
<1>
FWP-250A
250
5A0077
<1>
FWP-250A
250
5A0099
<1>
FWP-250A
250
5A0125
<1>
FWP-350A
350
5A0145
<1>
FWP-350A
350
5A0192
<1>
FWP-600A
600
5A0242
<1>
FWP-600A
600
<1> 600 V class drives are not compliant with European Standards.
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
n
CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
M
M
W/T3
Drive
V/T2
U/T1
+1
_
W/T3
Drive
V/T2
U/T1
+1
_
+
_
Fuse
Fuse
DC power supply
(converter)
Figure C.2 Example of DC Power Supply Input (Two A1000 Drives Connected in Series)
Note:
1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.
Refer to Standard Connection Diagram on page 106
3. The recommended fuses and fuse holders are made by Fuji Electric.
C.1 European Standards
348
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide