beautypg.com

C4: torque compensation, C5: automatic speed regulator (asr) – Yaskawa CIMR-AU 200V Drives User Manual

Page 277

background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C3-22

(0241)

Motor 2 Slip

Compensation Primary

Delay Time

Slip Comp Time 2

Sets the slip compensation delay time used for motor 2.

Default:

<2>

Min.: 0 ms

Max.: 10000 ms

C3-23

(0242)

Motor 2 Slip

Compensation Limit

Silp Comp Limit2

Sets the upper limit for the slip compensation function for

motor 2. Set as a percentage of the motor rated slip (E4-02).

Default: 200%

Min.: 0

Max.: 250

C3-24

(0243)

Motor 2 Slip

Compensation Selection

During Regeneration

RegenSlpComp2

0: Disabled

1: Above 6 Hz

2: Lowst possbl spd

0: Disabled.

1: Enabled above 6 Hz.

2: Enabled whenever slip compensation is possible.

Default: 0

Range: 0 to 2

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameter E3-01, Motor 2 Control Mode Selection.

u

C4: Torque Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C4-01

(0215)

Torque Compensation

Gain

Torq Comp Gain

Sets the gain for the automatic torque (voltage) boost function

and helps to produce better starting torque. Used for motor 1.

Default:

<1>

Min.: 0.00

Max.: 2.50

C4-02

(0216)

Torque Compensation

Primary Delay Time 1

Torq Comp Time

Sets the torque compensation filter time.

Default:

<2>

Min.: 0 ms

Max.: 60000 ms

C4-03

(0217)

Torque Compensation at

Forward Start

F TorqCmp@start

Sets torque compensation at forward start as a percentage of

motor torque.

Default: 0.0%

Min.: 0.0

Max.: 200.0

C4-04

(0218)

Torque Compensation at

Reverse Start

R TorqCmp@start

Sets torque compensation at reverse start as a percentage of

motor torque.

Default: 0.0%

Min.: -200.0

Max.: 0.0

C4-05

(0219)

Torque Compensation

Time Constant

TorqCmp Delay T

Sets the time constant for torque compensation at forward start

and reverse start (C4-03 and C4-04).

Default: 10 ms

Min.: 0

Max.: 200

C4-06

(021A)

Torque Compensation

Primary Delay Time 2

Start Torq Time

Sets the torque compensation time 2.

Default: 150 ms

Min.: 0

Max.: 10000

C4-07

(0341)

Motor 2 Torque

Compensation Gain

TrqCmp Gain Mtr2

Sets the torque compensation gain used for motor 2.

Default: 1.00

Min.: 0.00

Max.: 2.50

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.

u

C5: Automatic Speed Regulator (ASR)

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C5-01

(021B) ASR Proportional Gain 1 ASR P Gain 1

Sets the proportional gain of the speed control loop (ASR).

Default:

<1>

Min.: 0.00
Max.: 300.00

<2>

C5-02

(021C) ASR Integral Time 1

ASR I Time 1

Sets the integral time of the speed control loop (ASR).

Default:

<1>

Min.: 0.000 s

Max.: 10.000 s

C5-03

(021D) ASR Proportional Gain 2 ASR P Gain 2

Sets the speed control gain 2 of the speed control loop (ASR). Default:

<1>

Min.: 0.00
Max.: 300.00

<2>

B.3 C: Tuning

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

277