beautypg.com

Yaskawa CIMR-AU 200V Drives User Manual

Page 351

background image

3.

Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.

4.

Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.

A

B

D

E

C

M

U/T1

V/T2

W/T3

U

V

W

A – Drive
B – 10 m max cable length between

drive and motor

C – Motor

D – Metal conduit
E – Ground wire should be as short as

possible.

Figure C.3 Installation Method

5.

Make sure the protective earthing conductor complies with technical standards and local safety regulations.

WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4A0414 to 4A1200, IEC/EN

61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing

conductor, or a protective earthing conductor with a cross-section of at least 10 mm

2

(Cu) or 16 mm

2

(Al) must be used. Failure to

comply may result in death or serious injury.

C

B

A

A – Braided shield cable
B – Metal panel

C – Cable clamp (conductive)

Figure C.4 Ground Area

6.

Connect a DC link choke to minimize harmonic distortion.

Refer to DC Link Chokes for IEC/EN 61000-3-2

Compliance on page 355

.

C.1 European Standards

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

351

C

Standards Compliance