C.3 safe disable input function – Yaskawa CIMR-AU 200V Drives User Manual
Page 369

The input can use the internal power supply of the drive or an external power supply and it will support Sink mode or Source
mode. the mode selected for the digital input terminals S1 to S8 by switch S3 will also be used for the Safe Disable inputs.
Refer to Sinking/Sourcing Mode for Digital Inputs on page 135
The Safe Disable Monitor uses a single channel photocoupler output.
Refer to Output Terminals on page 131
for signal
specifications when using this output.
24 Vdc
Safety
Outputs
Power Module P
N
Motor
Gate Block 2
Gate Block 1
Control
Circuit
Main Power
H1
H2
HC
Drive
Slide Switch S6
Jumper S3
Setting:
SOURCE
>=1
DM+
DM-
Feedback
Safety Relay or PLC
with safety functionality
N.C.
N.O.
Figure C.12 Safe Disable Function Wiring Example (SINK Mode)
n
Disabling and Enabling the Drive Output (“Safe Torque Off”)
Note:
Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,
ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
illustrates the Safe Disable input operation.
H1, H2 Input
Drive Output
ON (Safe Disable off)
Normal operation
OFF (Safe Disable activated)
Safe Torque-Off
Run Command
Run
Stop
Baseblock (Not Safe!)
Output
Frequency
Motor coasts
to stop
Run Command must be
released to deactivate
Safe Disable
Drive is ready for
operation
Figure C.13 Safe Disable Operation
Entering the “Safe Torque Off” State
Note:
Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,
ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Whenever either one Safe Disable input or both inputs open, the motor torque is shut off by switching off the drive output. If
the motor was running before the Safe Disable inputs opened, then the motor will coast to stop, regardless of the stopping
method set in parameter b1-03.
Notice that the “Safe Torque Off” state can only be achieved using the Safe Disable function. Removing the Run command
stops the drive and shuts the output off (baseblock), but does not create a “Safe Torque Off” status.
Note:
To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor has completely
stopped.
Returning to Normal Operation after Safe Disable
Note:
Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,
ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
C.3 Safe Disable Input Function
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
369
C
Standards Compliance