beautypg.com

6 main circuit wiring – Yaskawa CIMR-AU 200V Drives User Manual

Page 127

background image

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

5A0062

R/L1, S/L2, T/L3

4

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

4

10 to 4/0

⊖, ⊕1

4 to 4/0

⊕3

6 to 4/0

4

4

5A0077

R/L1, S/L2, T/L3

3

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

3

10 to 4/0

⊖, ⊕1

3 to 4/0

⊕3

6 to 4/0

4

4

5A0099

R/L1, S/L2, T/L3

1/0

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

1

10 to 4/0

⊖, ⊕1

2 to 4/0

⊕3

4 to 4/0

4

4

5A0125

R/L1, S/L2, T/L3

2/0

1 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

2/0

1 to 300

⊖, ⊕1

2/0 to 3/0

⊕3

1 to 1/0

3

4 to 300

5A0145

R/L1, S/L2, T/L3

3/0

2/0 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

3/0

2/0 to 300

⊖, ⊕1

3/0 to 4/0

⊕3

1/0 to 2/0

3

4 to 300

5A0192

R/L1, S/L2, T/L3

300

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

250

2/0 to 600

⊖, ⊕1

2/0 to 400

⊕3

2/0 to 250

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

5A0242

R/L1, S/L2, T/L3

400

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

350

2/0 to 600

⊖, ⊕1

2/0 to 500

⊕3

250 to 300

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

Note:

When connecting peripheral devices or options to terminals

⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For

more information, contact Yaskawa or your nearest sales representative.

3.6 Main Circuit Wiring

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

127

3

Electrical Installation