Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0062
R/L1, S/L2, T/L3
4
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
4
10 to 4/0
⊖, ⊕1
–
4 to 4/0
⊕3
–
6 to 4/0
4
4
5A0077
R/L1, S/L2, T/L3
3
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
3
10 to 4/0
⊖, ⊕1
–
3 to 4/0
⊕3
–
6 to 4/0
4
4
5A0099
R/L1, S/L2, T/L3
1/0
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
1
10 to 4/0
⊖, ⊕1
–
2 to 4/0
⊕3
–
4 to 4/0
4
4
5A0125
R/L1, S/L2, T/L3
2/0
1 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
1 to 300
⊖, ⊕1
–
2/0 to 3/0
⊕3
–
1 to 1/0
3
4 to 300
5A0145
R/L1, S/L2, T/L3
3/0
2/0 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
3/0
2/0 to 300
⊖, ⊕1
–
3/0 to 4/0
⊕3
–
1/0 to 2/0
3
4 to 300
5A0192
R/L1, S/L2, T/L3
300
2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
250
2/0 to 600
⊖, ⊕1
–
2/0 to 400
⊕3
–
2/0 to 250
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3
400
2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
350
2/0 to 600
⊖, ⊕1
–
2/0 to 500
⊕3
–
250 to 300
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
Note:
When connecting peripheral devices or options to terminals
⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
3.6 Main Circuit Wiring
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
127
3
Electrical Installation