beautypg.com

B.12 t: motor tuning, T1: induction motor auto-tuning – Yaskawa CIMR-AU 200V Drives User Manual

Page 331

background image

B.12 T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance.

u

T1: Induction Motor Auto-Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

T1-00

(0700)

Motor 1/Motor 2

Selection

Select Motor

1: 1st Motor

2: 2nd Motor

1: Motor 1 (sets E1-oo, E2-oo)

2: Motor 2 (sets E3-oo, E4-oo)

Default: 1

Range: 1, 2

T1-01

(0701)

<1>

Auto-Tuning Mode

Selection

Tuning Mode Sel

0: Standard Tuning

1: Tune-No Rotate1

2: Term Resistance

3: V/f Engy Sav Tun

4: Tune-No Rotate2

5: Tune-No Rotate3

8:

9:

0: Rotational Auto-Tuning

1: Stationary Auto-Tuning 1

2: Stationary Auto-Tuning for Line-to-Line Resistance

3: Rotational Auto-Tuning for V/f Control (necessary for Energy

Savings and Speed Estimation Speed Search)

4: Stationary Auto-Tuning 2
5: Stationary Auto-Tuning 3

<2>

8: Inertia Tuning (perform Rotational Auto-Tuning prior to

Inertia Tuning)

9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to

ASR Gain Auto-Tuning)

Note:

1. Setting 5 is not available in models 4A0930 and

4A1200.

2. Settings 8 and 9 may not be available when

gears are between the machine and the motor

shaft.

Default: 0

<3>

Range: 0 to 5; 8,

9

T1-02

(0702)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power as specified on the motor nameplate.

Note:

Use the following formula to convert horsepower

into kilowatts:

1HP = 0.746 kW.

Default:

<4>

Min.: 0.00 kW

Max.: 650.00

kW

T1-03

(0703)

Motor Rated Voltage

Rated Voltage

Sets the motor rated voltage as specified on the motor nameplate. Default: 200.0

V

<5>

Min: 0.0
Max: 255.0

<5>

T1-04

(0704)

Motor Rated Current

Rated Current

Sets the motor rated current as specified on the motor nameplate. Default:

<4>

Min.: 10% of

drive rated

current

Max.: 200% of

drive rated

current

T1-05

(0705)

Motor Base Frequency Rated Frequency

Sets the rated frequency of the motor as specified on the motor

nameplate.

Default: 60.0

Hz

Min.: 0.0

Max.: 400.0

T1-06

(0706)

Number of Motor Poles Number of Poles

Sets the number of motor poles as specified on the motor

nameplate.

Default: 4

Min.: 2

Max.: 48

T1-07

(0707)

Motor Base Speed

Rated Speed

Sets the rated speed of the motor as specified on the motor

nameplate.

Default: 1750 r/

min

Min.: 0

Max.: 24000

T1-08

(0708)

PG Number of Pulses

Per Revolution

PG Pulses/Rev

Sets the number of pulses per revolution for the PG being used

(pulse generator or encoder).

Default: 1024

ppr

Min.: 1

Max.: 60000

T1-09

(0709)

Motor No-Load Current

(Stationary Auto-

Tuning)

No-Load Current

Sets the no-load current for the motor. After setting the motor

capacity to T1-02 and the motor rated current to T1-04, this

parameter will automatically display the no-load current for a

standard 4-pole Yaskawa motor. Enter the no-load current as

indicated on the motor test report.

Default: –

Min.: 0 A

Max.: T1-04

T1-10

(070A)

Motor Rated Slip

(Stationary Auto-

Tuning)

Motor Rated Slip

Sets the motor rated slip. After setting the motor capacity to

T1-02, this parameter will automatically display the motor slip

for a standard 4-pole Yaskawa motor. Enter the motor slip as

indicated on the motor test report.

Default: –

Min.: 0.00 Hz

Max.: 20.00 Hz

B.12 T: Motor Tuning

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

331

B

Parameter List