B.3 c: tuning, C1: acceleration and deceleration times – Yaskawa CIMR-AU 200V Drives User Manual
Page 275

B.3 C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier frequency
selections.
u
C1: Acceleration and Deceleration Times
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
C1-01
(0200)
Acceleration Time 1
Accel Time 1
Sets the time to accelerate from 0 to maximum frequency.
Default: 10.0 s
Min.: 0.0
Max.: 6000.0
<1>
C1-02
(0201)
Deceleration Time 1
Decel Time 1
Sets the time to decelerate from maximum frequency to 0.
C1-03
(0202)
Acceleration Time 2
Accel Time 2
Sets the time to accelerate from 0 to maximum frequency.
Default: 10.0 s
Min.: 0.0
Max.: 6000.0
<1>
C1-04
(0203)
Deceleration Time 2
Decel Time 2
Sets the time to decelerate from maximum frequency to 0.
C1-05
(0204)
Acceleration Time 3
(Motor 2 Accel Time 1) Accel Time 3
Sets the time to accelerate from 0 to maximum frequency.
Default: 10.0 s
Min.: 0.0
Max.: 6000.0
<1>
C1-06
(0205)
Deceleration Time 3
(Motor 2 Decel Time 1) Decel Time 3
Sets the time to decelerate from maximum frequency to 0.
C1-07
(0206)
Acceleration Time 4
(Motor 2 Accel Time 2) Accel Time 4
Sets the time to accelerate from 0 to maximum frequency.
Default: 10.0 s
Min.: 0.0
Max.: 6000.0
<1>
C1-08
(0207)
Deceleration Time 4
(Motor 2 Decel Time 2) Decel Time 4
Sets the time to decelerate from maximum frequency to 0.
C1-09
(0208)
Fast Stop Time
Fast Stop Time
Sets the time for the Fast Stop function.
Note:
Parameter setting cannot be changed when the
drive is operating the motor in models 4A0930
and 4A1200.
Default: 10.0 s
Min.: 0.0
Max.: 6000.0
<1>
–
C1-10
(0209)
Accel/Decel Time
Setting Units
Acc/Dec Units
0: 0.01 Seconds
1: 0.1 Seconds
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
Default: 1
Range: 0, 1
–
C1-11
(020A)
Accel/Decel Time
Switching Frequency
Acc/Dec SW Freq
Sets the frequency to switch between accel/decel time settings Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
–
<1> Setting range value is determined by parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
B.3 C: Tuning
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
275
B
Parameter List