H4: analog outputs – Yaskawa CIMR-AU 200V Drives User Manual
Page 310

H3 Multi-Function Analog Input Settings
H3-oo
Setting
Function
LCD Display
Description When Output Is 100%
Page
C
PID setpoint
PID Set Point
10 V = 100%
–
D
Frequency bias
Freq Ref Bias 2
10 V = E1-04 (maximum output frequency)
–
E
Motor temperature
(PTC input)
Motor PTC
10 V = 100%
–
F
Through mode
Not Used
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
–
10
Forward torque limit
Fwd Torque Limit
10 V = Motor rated torque
–
11
Reverse torque limit
Rev Torque Limit
10 V = Motor rated torque
–
12
Regenerative torque
limit
Regen Torq Limit
10 V = Motor rated torque
–
13
Torque reference/
Torque limit
Torque Reference
10 V = Motor rated torque
–
14
Torque compensation
Torque Comp
10 V = Motor rated torque
–
15
General torque limit
Torque Limit
10 V = Motor rated torque
–
16
Differential PID
feedback
PID Feedback 2
10 V = 100%
–
17
Motor Thermistor
(NTC)
Moter temp (NTC)
10 V = -9 °C
0 V = +234 °C
Note:
This setting is only available in models 4A0930 and 4A1200.
–
1F
Through mode
Not Used
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
–
30 to 32 DriveWorksEZ
analog input 1 to 3
–
Output is determined by the function selected using DWEZ.
–
u
H4: Analog Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H4-01
(041D)
Multi-Function Analog
Output Terminal FM
Monitor Selection
Term FM FuncSel
Selects the data to be output through multi-function analog
output terminal FM.
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter “103” for U1-03.
Default: 102
Range: 000 to
999
H4-02
(041E)
Multi-Function Analog
Output Terminal FM
Gain
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Default: 100.0%
Min.: -999.9
Max.: 999.9
H4-03
(041F)
Multi-Function Analog
Output Terminal FM
Bias
Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-04
(0420)
Multi-Function Analog
Output Terminal AM
Monitor Selection
Terminal AM Sel
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter “103” for U1-03.
Default: 103
Range: 000 to
999
H4-05
(0421)
Multi-Function Analog
Output Terminal AM
Gain
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of
the selected monitor value.
Default: 50.0%
Min.: -999.9
Max.: 999.9
H4-06
(0422)
Multi-Function Analog
Output Terminal AM
Bias
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-07
(0423)
Multi-Function Analog
Output Terminal FM
Signal Level Selection
Term FM Lvl Sel
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
B.7 H Parameters: Multi-Function Terminals
310