E2-01: motor rated current – Yaskawa CIMR-AU 200V Drives User Manual
Page 175

n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
10% to 200% of the drive
rated current
<1>
Determined by
C6-01 and o2-04
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
Note:
An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly to
prevent this error.
n
H1-01 to H1-08: Functions for Terminals S1 to S8
.
No.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to 9F
40 (F)
<1>
: Forward Run Command (2-Wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to 9F
41 (F)
<1>
: Reverse Run Command (2-Wire sequence)
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to 9F
24: External Fault
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 9F
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to 9F
3 (0)
<1>
: Multi-Step Speed Reference 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to 9F
4 (3)
<1>
: Multi-Step Speed Reference 2
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 9F
6 (4)
<1>
: Jog Reference Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 9F
8: External Baseblock Command
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Table 4.26 Multi-Function Digital Input Terminal Settings
Setting
Function
Page
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
–
2
External Reference 1/2 Selection
–
3
Multi-Step Speed Reference 1
–
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference Selection
–
7
Accel/Decel Time Selection 1
–
8
Baseblock Command (N.O.)
–
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
–
B
Drive Overheat Alarm (oH2)
–
C
Analog Terminal Input Selection
–
D
PG Encoder Disable
–
E
ASR integral reset
–
F
Through Mode
–
10
Up Command
–
11
Down Command
12
Forward Jog
–
13
Reverse Jog
14
Fault Reset
–
15
Fast Stop (N.O.)
–
Setting
Function
Page
16
Motor 2 Selection
–
17
Fast Stop (N.C.)
–
18
Timer Function Input
–
19
PID Disable
–
1A
Accel/Decel Time Selection 2
–
1B
Program Lockout
–
1E
Reference Sample Hold
–
20 to 2F External Fault
–
30
PID Integral Reset
–
31
PID Integral Hold
–
32
Multi-Step Speed Reference 4
–
34
PID Soft Starter Cancel
–
35
PID Input Level Selection
–
40
Forward Run Command (2-Wire sequence)
–
41
Reverse Run Command (2-Wire sequence)
42
Run Command (2-Wire sequence 2)
–
43
FWD/REV Command (2-Wire sequence 2)
44
Offset Frequency 1
–
45
Offset Frequency 2
46
Offset Frequency 3
47
Node Setup
–
60
DC Injection Braking Command
–
4.6 Basic Drive Setup Adjustments
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
175
4
Start-Up Programming & Operation