Terminal am/fm signal selection, Terminal dm+ and dm- output signal selection, Refer to terminal – Yaskawa CIMR-AU 200V Drives User Manual
Page 138: 8 control i/o connections

u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Table 3.17 Jumper S5 Settings
Terminal
Voltage Output
Current Output
Terminal AM
AM
FM
V
I
AM
FM
V
I
Terminal FM
AM
FM
V
I
AM
FM
V
I
Table 3.18 Parameter H4-07 and H4-08 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal AM signal level selection
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
0 to 2
0
H4-08
Terminal FM signal level selection
u
Terminal DM+ and DM- Output Signal Selection
Slide switch S6 selects N.C. or N.O. as the state of the DM+ and DM- terminals for EDM output. The switch is initially set
to N.C. Slide switch S6 is available on terminal board ETC74030o.
Table 3.19 EDM Switch Settings
S2 Position
Description
N.O.
Normally open
N.C.
Normally closed (default setting)
Note:
Refer to Safe Disable Input Function on page 368