H2: multi-function digital outputs, For descriptions of setting values – Yaskawa CIMR-AU 200V Drives User Manual
Page 305

H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function
LCD Display
Description
Page
62
External Speed Search
command 2
Speed Search 2
Closed: Activates Current Detection Speed Search from the frequency reference.
–
63
Field weakening
Field Weak
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
–
65
KEB Ride-Thru 1 (N.C.) KEB Ridethru NC
Open: KEB Ride-Thru 1 enabled.
–
66
KEB Ride-Thru 1 (N.O.) KEB Ridethru NO
Closed: KEB Ride-Thru 1 enabled.
–
67
Communications test
mode
Comm Test Mode
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the
test completes successfully.
–
68
High Slip Braking
(HSB)
HighSlipBraking
Closed: Activates High Slip Braking to stop the drive during a Run command.
–
6A
Drive enable
Drive Enable
Open: Drive disabled. If this input is opened during run, the drive will stop as
specified by b1-03.
Closed: Ready for operation.
–
71
Speed/Torque control
Sswitch
Spd/Trq Ctl Chng
Open: Speed Control
Closed: Torque Control
–
72
Zero servo
Zero Servo Cmd
Closed: Zero Servo enabled
–
75
Up 2 command
Up Command 2
Used to control the bias added to the frequency reference by the Up/Down 2
function. The Up 2 and Down 2 commands must always be used in conjunction
with one another.
–
76
Down 2 command
Down Command 2
Used to control the bias added to the frequency reference by the Up/Down 2
function. The Up 2 and Down 2 commands must always be used in conjunction
with one another.
–
77
ASR gain switch
ASR Gain Switch
Open: ASR proportional gain 1 (C5-01)
Closed: ASR proportional gain 2 (C5-03)
–
78
External torque
reference polarity
inversion
Tref Sign Change
Open: Forward torque reference.
Closed: Reverse polarity.
–
7A
KEB Ride-Thru 2 (N.C.) KEB Ridethru2NC
Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single
Drive KEB Ride-Thru 2.
–
7B
KEB Ride-Thru 2 (N.O.) KEB Ridethru2NO
Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single
Drive KEB Ride-Thru 2.
–
7C
Short circuit braking
(N.O.)
SC Brake (NO)
Closed: Short Circuit Braking enabled
–
7D
Short circuit braking
(N.C.)
SC Brake (NC)
Open: Short Circuit Braking enabled
–
7E
Forward/reverse
detection
(V/f Control with Simple
PG feedback)
PG Rotate Rev
Direction of rotation detection (for V/f with Simple PG Feedback)
–
7F
PID Bi-Directional
Enable
PID BiDir Enable
Reserved.
–
90 to 97 DriveWorksEZ
digital inputs 1 to 8
–
Reserved for DWEZ input functions
–
9F
DriveWorksEZ disable DWEZ Disable
Open: DWEZ enabled
Closed: DWEZ disabled
–
u
H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-01
(040B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
Refer to H2 Multi-Function Digital Output Settings on pages
for descriptions of setting values.
Default: 0
Range: 0 to 192
H2-02
(040C)
Terminal M3-M4
function selection
(relay)
P1/PC Func Sel
Default: 1
Range: 0 to 192
H2-03
(040D)
Terminal M5-M6
function selection
(relay)
P2/PC Func Sel
Default: 2
Range: 0 to 192
B.7 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
305
B
Parameter List