beautypg.com

H2: multi-function digital outputs, For descriptions of setting values – Yaskawa CIMR-AU 200V Drives User Manual

Page 305

background image

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

62

External Speed Search

command 2

Speed Search 2

Closed: Activates Current Detection Speed Search from the frequency reference.

63

Field weakening

Field Weak

Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.

65

KEB Ride-Thru 1 (N.C.) KEB Ridethru NC

Open: KEB Ride-Thru 1 enabled.

66

KEB Ride-Thru 1 (N.O.) KEB Ridethru NO

Closed: KEB Ride-Thru 1 enabled.

67

Communications test

mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the

test completes successfully.

68

High Slip Braking

(HSB)

HighSlipBraking

Closed: Activates High Slip Braking to stop the drive during a Run command.

6A

Drive enable

Drive Enable

Open: Drive disabled. If this input is opened during run, the drive will stop as

specified by b1-03.

Closed: Ready for operation.

71

Speed/Torque control

Sswitch

Spd/Trq Ctl Chng

Open: Speed Control

Closed: Torque Control

72

Zero servo

Zero Servo Cmd

Closed: Zero Servo enabled

75

Up 2 command

Up Command 2

Used to control the bias added to the frequency reference by the Up/Down 2

function. The Up 2 and Down 2 commands must always be used in conjunction

with one another.

76

Down 2 command

Down Command 2

Used to control the bias added to the frequency reference by the Up/Down 2

function. The Up 2 and Down 2 commands must always be used in conjunction

with one another.

77

ASR gain switch

ASR Gain Switch

Open: ASR proportional gain 1 (C5-01)

Closed: ASR proportional gain 2 (C5-03)

78

External torque

reference polarity

inversion

Tref Sign Change

Open: Forward torque reference.

Closed: Reverse polarity.

7A

KEB Ride-Thru 2 (N.C.) KEB Ridethru2NC

Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single

Drive KEB Ride-Thru 2.

7B

KEB Ride-Thru 2 (N.O.) KEB Ridethru2NO

Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single

Drive KEB Ride-Thru 2.

7C

Short circuit braking

(N.O.)

SC Brake (NO)

Closed: Short Circuit Braking enabled

7D

Short circuit braking

(N.C.)

SC Brake (NC)

Open: Short Circuit Braking enabled

7E

Forward/reverse

detection

(V/f Control with Simple

PG feedback)

PG Rotate Rev

Direction of rotation detection (for V/f with Simple PG Feedback)

7F

PID Bi-Directional

Enable

PID BiDir Enable

Reserved.

90 to 97 DriveWorksEZ

digital inputs 1 to 8

Reserved for DWEZ input functions

9F

DriveWorksEZ disable DWEZ Disable

Open: DWEZ enabled

Closed: DWEZ disabled

u

H2: Multi-Function Digital Outputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H2-01

(040B)

Terminal M1-M2

function selection

(relay)

M1-M2 Func Sel

Refer to H2 Multi-Function Digital Output Settings on pages

306

to

308

for descriptions of setting values.

Default: 0

Range: 0 to 192

177

H2-02

(040C)

Terminal M3-M4

function selection

(relay)

P1/PC Func Sel

Default: 1

Range: 0 to 192

177

H2-03

(040D)

Terminal M5-M6

function selection

(relay)

P2/PC Func Sel

Default: 2

Range: 0 to 192

177

B.7 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

305

B