• Use shielded wire for the PG encoder signal lines.
• Use separate conduit or cable tray dividers to separate option control wiring, main circuit input power wiring, and motor

output power cables.

PG-X3 Interface Circuit

26LS32 level

26LS31 level

PG X3

PG Encoder

A ,B ,Z

A+,B+,Z+

600

a ,b ,z

a+,b+,z+

SG

Monitor Signals

A,B,Z

A,B,Z 26LS31 level

Figure 7.12 PG-X3 Interface Circuit

PG-X3 Terminal Functions

Table 7.7 PG-X3 Option Terminal Functions

Terminal Block

Terminal

Function

Description

IG

IP

+

A

-

A

-Z

D

S

EF

Z+

+

B

-

B

TB1

TB2

SG

a+
a-
b+

b-
z+
z-

TB1

A+

A pulse signal input

• Inputs for the A channel, B channel, and Z

pulses from the PG encoder

• Signal level matches RS-422

A–

A inverse pulse signal input

B+

B pulse signal input

B–

B inverse pulse signal input

Z+

Z pulse signal input

Z–

Z inverse pulse signal input

SD

NC pin (open)

Open connection port for use when cable

shields should not be grounded

FE

Ground

Used as the shield ground termination point.

TB2

IP

PG encoder power supply

• Output voltage: 12.0 V ± 5% or 5.5 V ±

5%

• Max. output current: 200 mA

<1>

IG

PG encoder power supply common

SG

Monitor signal common

• Output signal for monitoring A channel, B

channel, and Z pulses from the PG encoder

• Signal level matches RS-422

a+

A pulse monitor signal

a–

A pulse inverse monitor signal

b+

B pulse monitor signal

b–

B pulse inverse monitor signal

z+

Z pulse monitor signal

z–

Z pulse inverse monitor signal

<1> A separate UL-listed class 2 power supply is necessary when the PG requires more than 200 mA to operate.

PG Encoder Power Supply Voltage

For the PG-X3 option, set the voltage for the PG encoder power supply using jumper CN3 located on the option. Position the

jumper as shown in

Table 7.8

to select the voltage level.

NOTICE: The positioning of jumper CN3 selects the PG encoder power supply voltage (5.5 V or 12 V). Select the voltage level for the PG

encoder connected to the option and motor. If the wrong voltage is selected, the PG encoder may not operate properly or may become

damaged as a result.

Table 7.8 Setting the PG Encoder Power Supply Voltage (IP) with Jumper CN3

Voltage Level

5.5 V ± 5% (default)

12.0 V ± 5%

Jumper CN3

CN3

5.5 V 12 V

CN3

5.5 V 12 V

PG-X3 Wire Gauges and Tightening Torques

Wire gauge and torque specifications are listed in

Table 7.9

. For simpler and more reliable wiring, use crimp ferrules on the

wire ends. Refer to the option manuals for the wire size and torque specifications of other options.

7.1 Option Card Installation