Yaskawa CIMR-AU 200V Drives User Manual
Page 329

No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o4-05
(051D)
Capacitor Maintenance
Setting
BusCap Maint Set
Sets the value of the Maintenance Monitor for the capacitors. See
U4-05 to check when the capacitors may need to be replaced.
Default: 0%
Min.: 0
Max.: 150
–
o4-07
(0523)
DC Bus Pre-Charge
Relay Maintenance
Setting
ChrgCircMaintSet
Sets the value of the Maintenance Monitor for the soft charge
bypass relay. See U4-06 to check when the bypass relay may need
to be replaced.
Default: 0%
Min.: 0
Max.: 150
–
o4-09
(0525)
IGBT Maintenance
Setting
IGBT Maint Set
Sets the value of the Maintenance Monitor for the IGBTs. See
U4-07 for IGBT replacement times.
Default: 0%
Min.: 0
Max.: 150
–
o4-11
(0510) U2, U3 Initialization
Fault Data Init
0: Disabled
1: Enabled
0: U2-oo and U3-oo monitor data is not reset when the drive
is initialized using A1-03.
1: U2-oo and U3-oo monitor data is reset when the drive is
initialized using A1-03. Parameter is automatically reset to 0.
Default: 0
Range: 0, 1
–
o4-12
(0512)
kWh Monitor
Initialization
kWh Monitor Init
0: No Reset
1: Reset
0: U4-10 and U4-11 monitor data is not reset when the drive is
initialized using A1-03.
1: U4-10 and U4-11 monitor data is reset when the drive is
initialized using A1-03. Parameter is automatically reset to 0.
Default: 0
Range: 0, 1
–
o4-13
(0528)
Number of Run
Commands Counter
Initialization
Run Counter Init
0: No Reset
1: Reset
0: U4-02 monitor data is not reset when the drive is initialized
using A1-03.
1: U4-02 monitor data is reset when the drive is initialized using
A1-03. Parameter is automatically reset to 0.
Default: 0
Range: 0, 1
–
B.10 o: Operator-Related Settings
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
329