o4-05

(051D)

Capacitor Maintenance

Setting

BusCap Maint Set

Sets the value of the Maintenance Monitor for the capacitors. See

U4-05 to check when the capacitors may need to be replaced.

Default: 0%

Min.: 0

Max.: 150

o4-07

(0523)

DC Bus Pre-Charge

Relay Maintenance

Setting

ChrgCircMaintSet

Sets the value of the Maintenance Monitor for the soft charge

bypass relay. See U4-06 to check when the bypass relay may need

to be replaced.

Default: 0%

Min.: 0

Max.: 150

o4-09

(0525)

IGBT Maintenance

Setting

IGBT Maint Set

Sets the value of the Maintenance Monitor for the IGBTs. See

U4-07 for IGBT replacement times.

Default: 0%

Min.: 0

Max.: 150

o4-11

(0510) U2, U3 Initialization

Fault Data Init

0: Disabled

1: Enabled

0: U2-oo and U3-oo monitor data is not reset when the drive

is initialized using A1-03.

1: U2-oo and U3-oo monitor data is reset when the drive is

initialized using A1-03. Parameter is automatically reset to 0.

Default: 0

Range: 0, 1

o4-12

(0512)

kWh Monitor

Initialization

kWh Monitor Init

0: No Reset

1: Reset

0: U4-10 and U4-11 monitor data is not reset when the drive is

initialized using A1-03.

1: U4-10 and U4-11 monitor data is reset when the drive is

initialized using A1-03. Parameter is automatically reset to 0.

Default: 0

Range: 0, 1

o4-13

(0528)

Number of Run

Commands Counter

Initialization

Run Counter Init

0: No Reset

1: Reset

0: U4-02 monitor data is not reset when the drive is initialized

using A1-03.

1: U4-02 monitor data is reset when the drive is initialized using

A1-03. Parameter is automatically reset to 0.

Default: 0

Range: 0, 1

B.10 o: Operator-Related Settings

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

329

B

Parameter List