Yaskawa CIMR-AU 200V Drives User Manual
Page 256

u
Three-Phase 600 V Class Drive Models 5A0041 to 5A0099
Table A.9 Power Ratings Continued (Three-Phase 600 V Class)
Item
Specification
Drive Models
5A0041
5A0052
5A0062
5A0077
5A0099
Maximum Applicable Motor Capacity (HP)
<1>
ND Rating
40
50
60
75
100
HD Rating
25-30
40
50-60
50-60
75
Input
Input Current (A)
<2>
ND Rating
44
54
66
80
108
HD Rating
33
44
54
66
80
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage Fluctuation
-10 (-15) to +10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
50
62
75
91
123
HD Rating
38
50
62
75
91
Output
Rated Output Capacity (kVA)
<3>
ND Rating
<4>
41
52
62
77
99
HD Rating
32
<5>
41
<5>
52
<5>
62
<5>
77
<6>
Rated Output Current (A)
ND Rating
<4>
41
52
62
77
99
HD Rating
32
<5>
41
<5>
52
<5>
62
<5>
77
<6>
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User adjustable between 2 and 10 kHz
User
adjustable
between 2 and
8 kHz
Maximum Output Voltage (V)
Three-phase 500 to 600 Vac (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
A.2 Power Ratings
256