Yaskawa CIMR-AU 200V Drives User Manual
Page 307

H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function
LCD Display
Description
Page
E
Fault
Fault
Closed: Fault occurred (this excludes CPF00 and CPF01).
–
F
Through mode
Not Used
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
–
10
Minor fault
Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
expected life span.
–
11
Fault reset command
active
Reset Cmd Active
Closed: The drive has received a reset command from the multi-function input
terminals or from a serial network, or the RESET key on the digital operator has
been pressed.
–
12
Timer output
Timer Output
Closed: Timer output.
–
13
Speed agree 2
Fref/Fout Agree2
Closed: When drive output frequency equals the frequency reference ±L4-04.
Note:
This setting is not available in models 4A0930 and 4A1200.
–
14
User-set speed agree 2
Fref/Set Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
–
15
Frequency detection 3
Freq Detect 3
Closed: When the drive output frequency is less than or equal to the value in L4-03
±L4-04.
–
16
Frequency detection 4
Freq Detect 4
Closed: When the output frequency is greater than or equal to the value in L4-03
±L4-04.
–
17
Torque detection 1
(N.C.)
Trq Det 1 N.C.
Open: Overtorque or undertorque has been detected.
–
18
Torque detection 2
(N.O.)
Trq Det 2 N.O.
Closed: Overtorque or undertorque has been detected.
19
Torque detection 2
(N.C.)
Trq Det 2 N.C.
Open: Overtorque or undertorque has been detected.
–
1A
During reverse
Reverse Dir
Closed: Drive is running in the reverse direction.
–
1B
During baseblock (N.C.) BaseBlk 2
Open: Drive has entered the baseblock state (no output voltage).
–
1C
Motor 2 selection
Motor 2 Selected
Closed: Motor 2 is selected by a digital input (H1-oo = 16)
–
1D
During regeneration
Regenerating
Closed: Motor is regenerating energy into the drive.
–
1E
Restart enabled
Dur Flt Restart
Closed: An automatic restart is performed
–
1F
Motor overload alarm
(oL1)
Overload (OL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
this alarm.
–
20
Drive overheat pre-
alarm (oH)
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
–
22
Mechanical weakening
detection
MechFatigue(OL5)
Closed: Mechanical weakening detected.
–
2F
Maintenance period
Maintenance
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
–
30
During torque limit
Torque Limit
Closed: When the torque limit has been reached.
–
31
During speed limit
Speed Limit
Closed: Speed limit has been reached.
–
32
During speed limit in
Torque Control
Spd Lim @ T Cont
Closed: Speed limit has been reached while using Torque Control.
–
33
Zero Servo complete
Zero Servo End
Closed: Zero Servo operation has finished.
–
37
During frequency output During RUN 2
Open: No frequency output from drive if stopped with baseblock, DC injection
braking during initial excitation, or short-circuit braking.
Closed: Drive is outputting a frequency.
–
38
Drive enabled
Drive Enable
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)
–
39
Watt hour pulse output Watt-hour Pulse
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
the kWh count.
–
3C
LOCAL/REMOTE
status
Local
Open: REMOTE
Closed: LOCAL
–
3D
During speed search
During SpdSrch
Closed: Speed Search is being executed.
–
3E
PID feedback low
PID Feedback Low
Closed: PID feedback level is too low.
–
3F
PID feedback high
PID FeedbackHigh
Closed: The PID feedback level is too high.
–
4A
During KEB Ride-Thru During KEB
Closed: KEB Ride-Thru is being performed.
–
4B
During short circuit
braking
During SC Brake
Closed: Short Circuit Braking is active.
–
B.7 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
307