L8: Drive Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-01

(04AD)

Internal Dynamic

Braking Resistor

Protection Selection

(ERF type)

DB Resistor Prot

0: Not Provided

1: Provided

0: Resistor overheat protection disabled

1: Resistor overheat protection enabled

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 0

Range: 0, 1

L8-02

(04AE) Overheat Alarm Level OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature exceeds the

L8-02 level.

Default:

<1>

Min.: 50 °C

Max.: 150 °C

L8-03

(04AF)

Overheat Pre-Alarm

Operation Selection

OH Pre-Alarm Sel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

4: Run@L8-19 Rate

0: Ramp to stop. A fault is triggered.

1: Coast to stop. A fault is triggered.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09. A fault is triggered.

3: Continue operation. An alarm is triggered.

4: Continue operation at reduced speed as set in L8-19.

Default: 3

Range: 0 to 4

L8-05

(04B1)

Input Phase Loss

Protection Selection

Inp Ph Loss Det

0: Disabled

1: Enabled

Selects the detection of input current phase loss, power supply

voltage imbalance, or main circuit electrolytic capacitor

deterioration.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

L8-07

(04B3)

Output Phase Loss

Protection Selection

Outp Ph Loss Det

0: Disabled

1: 1PH Loss Det

2: 2/3PH Loss Det

0: Disabled

1: Enabled (triggered by a single phase loss)

2: Enabled (triggered when two phases are lost)

Default: 1

Range: 0 to 2

L8-09

(04B5)

Output Ground Fault

Detection Selection

Grnd Flt Det Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default:

<1>

Range: 0, 1

L8-10

(04B6)

Heatsink Cooling Fan

Operation Selection

Fan On/Off Sel

0: Dur Run (OffDly)

1: Always On

0: Run with timer (Fan operates only during run and for L8-11

seconds after stop.)

1: Run always (Cooling fan operates whenever the drive is

powered up.)

Default: 0

Range: 0, 1

L8-11

(04B7)

Heatsink Cooling Fan

Off Delay Time

Fan Delay Time

Sets a delay time to shut off the cooling fan after the Run

command is removed when L8-10 = 0.

Default: 60 s

Min.: 0

Max.: 300

L8-12

(04B8)

Ambient Temperature

Setting

Ambient Temp

Enter the ambient temperature. This value adjusts the oL2

detection level.

Default: 40 °C

Min.: -10

Max.: 50

L8-15

(04BB)

oL2 Characteristics

Selection at Low Speeds

OL2 Sel @ L-Spd

0: Disabled

1: Enabled

0: No oL2 level reduction below 6 Hz.

1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. Default: 1

Range: 0, 1

L8-18

(04BE)

Software Current Limit

Selection

Soft CLA Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

L8-19

(04BF)

Frequency Reduction

Rate during Overheat

Pre-Alarm

Fc Red dur OHAlm

Specifies the frequency reference reduction gain at overheat pre-

alarm when L8-03 = 4.

Default: 0.8

Min.: 0.1

Max.: 0.9

L8-27

(04DD)

Overcurrent Detection

Gain

OC Level

Sets the gain for overcurrent detection as a percentage of the

motor rated current. Overcurrent is detected using the lower value

between the overcurrent level of the drive or the value set to

L8-27.

Default: 300.0%

Min.: 0.0
Max.: 400.0

<2>

L8-29

(04DF)

Current Unbalance

Detection (LF2)

LF2 Flt Det Sel

0: Disabled

1: Current&Voltage

2: Current Det Type

3: Voltage Det Type

For models 2A0004 to 2A0415, 4A0002 to 4A0675, and 5A0003

to 5A0242:

0: Disabled

1: Enabled (current and voltage detection)

2: Enabled (current detection)

3: Enabled (voltage detection)

For models 4A0930 and 4A1200:

0: Disabled

1: Enabled (current detection)

Default: 1

Range: 0 to 3

Range: 0, 1

B.8 L: Protection Function

320

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide