L7: torque limit – Yaskawa CIMR-AU 200V Drives User Manual

Page 319

background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L6-06

(04A6)

Torque Detection

Time 2

Torq Det 2 Time

Sets the time an overtorque or undertorque condition must exist

to trigger torque detection 2.

Default: 0.1 s

Min.: 0.0

Max.: 10.0

L6-08

(0468)

Mechanical Weakening

Detection Operation

Mech Fatigue Sel

0: Disabled

1: Alm Spd>L6-09

2: Alm [Spd]>L6-09

3: Flt Spd>L6-09

4: Flt [Spd]>L6-09

5: Alm Spd

6: Alm [Spd]

7: Flt Spd

8: Flt [Spd]

This function can detect an overtorque or undertorque in a certain

speed range as a result of machine fatigue. It is triggered by a

specified operation time and uses the oL1 detection settings

(L6-01 and L6-03).

0: Mechanical Weakening Detection disabled.

1: Continue running (alarm only). Detected when the speed

(signed) is greater than L6-09.

2: Continue running (alarm only). Detected when the speed (not

signed) is greater than L6-09.

3: Interrupt drive output (fault). Detected when the speed (signed)

is greater than L6-09.

4: Interrupt drive output (fault). Detected when the speed (not

signed) is greater than L6-09.

5: Continue running (alarm only). Detected when the speed

(signed) is less than L6-09.

6: Continue running (alarm only). Detected when the speed (not

signed) is less than L6-09.

7: Interrupt drive output (fault). Detected when the speed (signed)

is less than L6-09.

8: Interrupt drive output (fault). Detected when the speed (not

signed) is less than L6-09.

Default: 0

Range: 0 to 8

L6-09

(0469)

Mechanical Weakening

Detection Speed Level MechFat Det Spd

Sets the speed that triggers Mechanical Weakening Detection.

When L6-08 is set for an unsigned value, the absolute value is

used if the setting is negative.

Default: 110.0%

Min.: -110.0

Max.: 110.0

L6-10

(046A)

Mechanical Weakening

Detection Time

MechFat Det Time

Sets the time mechanical weakening has to be detected before an

alarm or fault is triggered.

Default: 0.1 s

Min.: 0.0

Max.: 10.0

L6-11

(046B)

Mechanical Weakening

Detection Start Time

MechFat Det Hour

Sets the operation time (U1-04) required before Mechanical

Weakening Detection is active.

Default: 0 h

Min.: 0

Max.: 65535

u

L7: Torque Limit

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L7-01

(04A7) Forward Torque Limit Torq Limit Fwd

Sets the torque limit value as a percentage of the motor rated

torque. Four individual quadrants can be set.

L7-01

L7-03

L7-02

L7-04

Output Torque

Positive Torque

REV

Negative Torque

FWD

Motor
r/min

Regeneration

Regeneration

Default: 200%

Min.: 0

Max.: 300

186

L7-02

(04A8) Reverse Torque Limit

Torq Limit Rev

Default: 200%

Min.: 0

Max.: 300

186

L7-03

(04A9)

Forward Regenerative

Torque Limit

Torq Lmt Fwd Rgn

Default: 200%

Min.: 0

Max.: 300

186

L7-04

(04AA)

Reverse Regenerative

Torque Limit

Torq Lmt Rev Rgn

Default: 200%

Min.: 0

Max.: 300

186

L7-06

(04AC)

Torque Limit Integral

Time Constant

Trq Lim I Time

Sets the integral time constant for the torque limit.

Default: 200 ms

Min: 5

Max: 10000

L7-07

(04C9)

Torque Limit Control

Method Selection during

Accel/Decel

Trq Lim d AccDec

P-ctrl @ Acc/Dec

I-ctrl @ Acc/Dec

0: Proportional control (changes to integral control at constant

speed). Use this setting when acceleration to the desired speed

should take precedence over the torque limit.

1: Integral control. Set L7-07 to 1 if the torque limit should take

precedence.

Default: 0

Range: 0, 1

L7-16

(0444D)

<1>

Torque Limit Process at

Start

TLim DlyTime Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

<1> Available in drive software versions PRG: 1018 and later.

B.8 L: Protection Function

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

319

B

Parameter List