Table 4.31

lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.

The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor

manufacturer.

Refer to Subchart A-3: Operation with Permanent Magnet Motors on page 155

for details on the Auto-Tuning

process and selection.

Figure 4.38 Motor Nameplate Example

Table 4.31 Auto-Tuning Input Data

Input Value

Input

Param.

Unit

Tuning Type (T2-01)

0

Motor Parameter Settings

1

Stationary

2

Stationary

Stator
Resis.

3

Z-Pulse

Offset

11

Back

EMF

Const.

13

High Freq.

Injection

14

Rotational

Control Mode

A1-02

5, 6, 7

5

6, 7

5

6, 7

5, 6, 7

7

7

6, 7

5

6

7

Motor Code (Hex.)

T2-02

<1>

<1>

<1>

Motor Type

T2-03

YES

YES

YES

YES

YES

Motor Rated Power

T2-04

kW

YES

YES

YES

YES

YES

YES

YES

Motor Rated
Voltage

T2-05

Vac

YES

YES

YES

YES

YES

YES

YES

Motor Rated
Current

T2-06

A

YES

YES

YES

YES

YES

YES

YES

YES

Motor Rated
Frequency

T2-07

Hz

YES

YES

YES

Number of Motor
Poles

T2-08

YES

YES

YES

YES

YES

YES

YES

Motor Rated Speed

T2-09

r/min

YES

YES

YES

YES

Stator Single-phase
Resistance

T2-10

Ω

YES

YES

YES

d-Axis Inductance

T2-11

mH

YES

YES

YES

q-Axis Inductance

T2-12

mH

YES

YES

YES

Induced Voltage
Constant Unit
Selection

T2-13

mVs/

rad

(elec.)

YES

YES

YES

Voltage Constant

<3>

T2-14

mVmin
(mech.)

YES

YES

YES

Tuning Pull-in
Current

T2-15

A

YES

YES

YES

YES

YES

PG Number of
Pulses Per
Revolution

T2-16

YES

<2>

YES

<2>

YES

<2>

YES

Z Pulse Offset

T2-17

deg

(mech.) YES

<2>

YES

<2>

YES

<2>

<1> Input the motor code when using a Yaskawa motor. Select “FFFF” when using a motor from another manufacturer.
<2> Input data is needed for CLV/PM only.
<3> Dependent upon T2-13 setting.

4.7 Auto-Tuning

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

189