Yaskawa CIMR-AU 200V Drives User Manual
Page 202

CPF02
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
CPF03
Control Board Connection Error
Connection error between the control board and the drive
CPF06
EEPROM Memory Data Error
Error in the data saved to EEPROM
Cause
Possible Solution
There is an error in EEPROM control circuit
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
The power supply was switched off while
parameters were being saved to the drive
Reinitialize the drive (A1-03 = 2220, 3330).
Digital Operator Display
Fault Name
CPF07
Terminal Board Connection Error
CPF08
Digital Operator Display
Fault Name
CPF11
RAM Fault
Digital Operator Display
Fault Name
CPF12
FLASH Memory Fault
Problem with the ROM (FLASH memory)
Digital Operator Display
Fault Name
CPF13
Watchdog Circuit Exception
Self-diagnostics problem.
Digital Operator Display
Fault Name
CPF14
Control Circuit Fault
CPU error (CPU operates incorrectly due to interference, etc.)
Digital Operator Display
Fault Name
CPF16
Clock Fault
Standard clock error.
Digital Operator Display
Fault Name
CPF17
Timing Fault
A timing error occurred during an internal process.
Digital Operator Display
Fault Name
CPF18
Control Circuit Fault
CPU error. Non-Maskable Interrupt (An unusual interrupt was triggered by interference, etc.)
Digital Operator Display
Fault Name
CPF19
Control Circuit Fault
CPU error (Manual reset due to interference, etc.)
or
CPF20 or CPF21
Control Circuit Error
CPF22
Hybrid IC Failure
CPF23
Control Board Connection Error
Connection error between the control board and the drive
CPF24
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
5.2 Fault Detection
202
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide