n8-54

(056D)

Voltage Error

Compensation Time

Constant

PM V Error CompT

Adjusts the value when hunting occurs at low speed. If hunting

occurs with sudden load changes, increase n8-54 in increments

of 0.1. Reduce this setting if oscillation occurs at start.

Default: 1.00 s

Min.: 0.00

Max.: 10.00

n8-55

(056E) Load Inertia

PMLoad wk2 Ratio

0: Less than 1:10

1: 1:10 to 1:30

2: 1:30 to 1:50

3: More than 1:50

Sets the ratio between motor and machine inertia.

0: Below 1:10

1: Between 1:10 and 1:30

2: Between 1:30 and 1:50

3: Beyond 1:50

Default: 0

Min.: 0

Max.: 3

n8-57

(0574)

High Frequency

Injection

PM Harm Inj Sel

0: Disabled

1: Enabled

0: Disabled. Disable when using an SPM motor.

1: Enabled. Use this setting to enhance the speed control range

when using an IPM motor.

Default: 0

Range: 0, 1

n8-62

(057D)

Output Voltage Limit

(for PM Motors)

PM Vout Limit

Prevents output voltage saturation. Should be set just below the

voltage provided by the input power supply.

Default: 200.0
V

<4>

Min.: 0.0
Max.: 230.0

<4>

n8-65

(065C)

Speed Feedback

Detection Control Gain

during ov Suppression

SFdbk G @OV Supp

Sets the gain used for internal speed feedback detection during

ov suppression.

Default: 1.50

Min.: 0.00

Max.: 10.00

n8-69

(065D) Speed Calculation Gain SpdSrch Gain

Sets the proportional gain for PLL control of an extended

observer.

There is normally no need to change this parameter from the

default value.

Default: 1.00

Min.: 0.00

Max.: 20.00

n8-72

(0655)

<1>

Speed Estimation

Method Selection

Spd Est method

0: Conventional

1: A1000 method

Sets the method to be used for estimating the speed.

0: Conventional method

1: A1000 method

There is normally no need to change this parameter from the

default value.

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 1

Range: 0, 1

n8-84

(02D3)

Initial Polarity

Estimation Timeout

Current

Polarity Det Curr

Sets the current to determine polarity for the initial polarity

calculation as a percentage of the motor rated current.

100% = Motor rated current

Note:

If an “Si” value is listed on a Yaskawa motor

nameplate, set n8-84 to “Si” value x 2.

Default: 100%

Min.: 0

Max.: 150

<1> Available in drive software versions PRG: 1018 and later.
<2> Default setting is determined by parameter n8-72, Speed Estimation Method Selection.

When n8-72 = 0, default is 50.0
When n8-72 = 1, default is 150.0.

<3> Default setting is determined by parameter E5-01, Motor Code Selection.
<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.