B.2 b: Application

Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID

control, the Dwell function, Energy Savings, and a variety of other application-related settings.

u

b1: Operation Mode Selection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b1-01

(0180)

Frequency Reference

Selection 1

Ref Source 1

0: Operator

1: Analog Input

2: Serial Com

3: Option PCB

4: Pulse Input

0: Digital operator

1: Analog input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse input (terminal RP)

Default: 1

Range: 0 to 4

159

b1-02

(0181)

Run Command

Selection 1

Run Source 1

0: Operator

1: Digital Inputs

2: Communication

3: Option PCB

0: Digital operator

1: Digital input terminals

2: MEMOBUS/Modbus communications

3: Option PCB

Default: 1

Range: 0 to 3

161

b1-03

(0182)

Stopping Method

Selection

Stopping Method

0: Ramp to Stop

1: Coast to Stop

2: DCInj to Stop

3: Coast w/Timer

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

Default: 0
Range: 0 to 3

<1>

161

b1-04

(0183)

Reverse Operation

Selection

Reverse Oper

0: Reverse Enabled

1: Reverse Disabled

0: Reverse enabled.

1: Reverse disabled.

Default: 0

Range: 0, 1

b1-05

(0184)

Action Selection below

Minimum Output

Frequency

Zero-Speed Oper

0: RUN at Freq Ref

1: STOP

2: RUN at Min Freq

RUN at Zero PRM

0: Operates according to frequency reference (E1-09 is

disabled).

1: Output shuts off (coast to stop if less than E1-09).

2: Operates according to E1-09 (frequency reference set to

E1-09).

3: Zero speed (frequency reference becomes zero when less than

E1-09).

Default: 0

Range: 0 to 3

b1-06

(0185)

Digital Input Reading

Cntl Input Scans

0: 1 Scan

1: 2 Scans

0: Input status is read once and processed immediately (for

quicker response)

1: Input is read twice and processed only if the status is the same

in both readings (robust against noisy signals)

Default: 1

Range: 0, 1

b1-07

(0186)

LOCAL/REMOTE Run

Selection

LOC/REM Dur Run

0: Cycle Extrn RUN

1: Accept Extrn RUN

0: An external Run command must be cycled at the new source

in order to be activated.

1: An external Run command at the new source is accepted

immediately.

Default: 0

Range: 0, 1

b1-08

(0187)

Run Command Selection

in Programming Mode

RUN dur PRG Mode

0: Run

Disabled@PRG

1: Run Enabled@PRG

2: Prg only @ Stop

0: Run command is not accepted while in Programming Mode.

1: Run command is accepted while in Programming Mode.

2: Prohibit entering Programming Mode during run.

Default: 0

Range: 0 to 2

b1-14

(01C3) Phase Order Selection

Rotation Sel

0: Standard

1: SwitchPhaseOrder

0: Standard

1: Switch phase order (reverses the direction of the motor)

Default: 0

Range: 0, 1

b1-15

(01C4)

Frequency Reference

Selection 2

Ref Source 2

0: Operator

1: Analog Input

2: Serial Com

3: Option PCB

4: Pulse Input

Enabled when an input terminal set for “External reference”

(H1-oo = 2) closes.

0: Digital operator

1: Terminals (analog input terminals)

2: MEMOBUS/Modbus communications

3: Option card

4: Pulse train input

Default: 0

Range: 0 to 4

b1-16

(01C5)

Run Command

Selection 2

Run Source 2

0: Operator

1: Digital Inputs

2: Communication

3: Option PCB

Enabled when a terminal set for “External reference”

(H1-oo = 2) closes.

0: Digital operator

1: Digital input terminals

2: MEMOBUS/Modbus communications

3: Option card

Default: 0

Range: 0 to 3

B.2 b: Application