C.2 ul and csa standards – Yaskawa CIMR-AU 200V Drives User Manual
Page 360

Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3
Machine No.
Die Jaw
4A0414
4/0 × 2P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 2P
4A0515
3/0 × 4P
3/0 × 4P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080
100-051-558
4/0 × 4P
4/0 × 4P
100-L12
TD-324,
TD-312
TP-100
100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 2P
4A0675
4/0 × 4P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 4P
4A0930
3/0 × 8P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080
100-051-558
4/0 × 8P
100-L12
TD-324,
TD-312
TP-100
100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 8P
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100
100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150
100-051-562
300 × 8P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Factory Recommended Branch Circuit Protection for UL Compliance
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral
devices if the cause cannot be identified.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in the tables
below.
Table C.7 Factory Recommended A1000 AC Drive Branch Circuit Protection (Normal Duty)
Drive Model
A1000 in Normal Duty Mode (C6-01 = 1)
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating
Amps
<3>
Bussman Semi-
conductor Fuse
Rating (Fuse
Ampere)
<4>
200 V Class
2A0004
0.75
3.9
15
6.25
10
FWH-70B (70)
2A0006
1 - 1.5
7.3
15
12
20
FWH-70B (70)
2A0008
2
8.8
15
15
25
FWH-70B (70)
2A0010
3
10.8
20
17.5
30
FWH-70B (70)
2A0012
3
13.9
25
20
40
FWH-70B (70)
2A0018
5
18.5
35
30
50
FWH-90B (90)
2A0021
7.5
24
45
40
70
FWH-90B (90)
C.2 UL and CSA Standards
360
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide