L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(049E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after the

following faults occur: GF, LF, oC, oH1, ov, PF, rH, rr, oL1, oL2,

oL3, oL4, STo, Uv1.

Default: 0

Min.: 0

Max.: 10

L5-02

(049F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

L5-04

(046C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault restarts. Default: 10.0 s

Min.: 0.5

Max.: 600.0

L5-05

(0467)

Fault Reset Operation

Selection

Fault Reset Sel

0: Continuous

1: Use L5-04 Time

0: Continuously attempt to restart while incrementing restart

counter only at a successful restart (same as F7 and G7).

1: Attempt to restart with the interval time set in L5-04 and

increment the restart counter with each attempt (same as V7).

Default: 0

Range: 0, 1

u

L6: Torque Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L6-01

(04A1)

Torque Detection

Selection 1

Torq Det 1 Sel

0: Disabled

1: OL Alm at SpdAgr

2: OL Alm dur RUN

3: OL Flt at SpdAgr

4: OL Flt dur RUN

5: UL Alm at SpdAgr

6: UL Alm dur RUN

7: UL Flt at SpdAgr

8: UL Flt dur RUN

0: Disabled

1: oL3 detection only active during speed agree, operation

continues after detection

2: oL3 detection always active during run, operation continues

after detection

3: oL3 detection only active during speed agree, output shuts

down on an oL3 fault

4: oL3 detection always active during run, output shuts down on

an oL3 fault

5: UL3 detection only active during speed agree, operation

continues after detection

6: UL3 detection always active during run, operation continues

after detection

7: UL3 detection only active during speed agree, output shuts

down on an oL3 fault

8: UL3 detection always active during run, output shuts down on

an oL3 fault

Default: 0

Range: 0 to 8

L6-02

(04A2)

Torque Detection

Level 1

Torq Det 1 Lvl

Sets the overtorque and undertorque detection level.

Default: 150%

Min.: 0

Max.: 300

L6-03

(04A3)

Torque Detection

Time 1

Torq Det 1 Time

Sets the time an overtorque or undertorque condition must exist

to trigger torque detection 1.

Default: 0.1 s

Min.: 0.0

Max.: 10.0

L6-04

(04A4)

Torque Detection

Selection 2

Torq Det 2 Sel

0: Disabled

1: OL Alm at SpdAgr

2: OL Alm dur RUN

3: OL Flt at SpdAgr

4: OL Flt dur RUN

5: UL Alm at SpdAgr

6: UL Alm dur RUN

7: UL Flt at SpdAgr

8: UL Flt dur RUN

0: Disabled

1: oL4 detection only active during speed agree, operation

continues after detection

2: oL4 detection always active during run, operation continues

after detection

3: oL4 detection only active during speed agree, output shuts

down on an oL4 fault

4: oL4 detection always active during run, output shuts down on

an oL4 fault

5: UL4 detection only active during speed agree, operation

continues after detection

6: UL4 detection always active during run, operation continues

after detection

7: UL4 detection only active during speed agree, output shuts

down on an oL4 fault

8: UL4 detection always active during run, output shuts down on

an oL4 fault

Default: 0

Range: 0 to 8

L6-05

(04A5)

Torque Detection

Level 2

Torq Det 2 Lvl

Sets the overtorque and undertorque detection level.

Default: 150%

Min.: 0

Max.: 300

B.8 L: Protection Function