Three-phase 200 v class, 6 main circuit wiring – Yaskawa CIMR-AU 200V Drives User Manual
Page 121

NOTICE: Do not connect a braking resistor to terminals
⊕1 or ⊖. Failure to comply may cause damage to the drive circuitry.
•
Refer to UL Standards Compliance on page 356
for information on UL compliance.
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of closed-
loop crimp terminals when wiring the drive main circuit terminals on models 2A0110 to 2A0415 and 4A0058 to 4A1200. Use
only the tools recommended by the terminal manufacturer for crimping.
Refer to Closed-Loop Crimp Terminal Size on page
for closed-loop crimp terminal recommendations.
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge
selections.
n
Three-Phase 200 V Class
Table 3.3 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0004
2A0006
2A0008
2A0010
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
<1>
14 to 10
2A0012
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
<1>
14 to 10
2A0018
R/L1, S/L2, T/L3
10
12 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
<1>
14 to 10
2A0021
R/L1, S/L2, T/L3
10
12 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
12 to 10
⊖, ⊕1, ⊕2
–
12 to 10
B1, B2
–
14 to 10
10
<1>
12 to 10
2A0030
R/L1, S/L2, T/L3
8
10 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
8
10 to 6
⊖, ⊕1, ⊕2
–
10 to 6
B1, B2
–
14 to 10
8
<2>
10 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
2A0040
R/L1, S/L2, T/L3
6
8 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
8
8 to 6
⊖, ⊕1, ⊕2
–
6
B1, B2
–
12 to 10
8
<2>
10 to 8
M5
2.0 to 2.5
(17.7 to 22.1)
2A0056
R/L1, S/L2, T/L3
4
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
4
6 to 4
⊖, ⊕1, ⊕2
–
6 to 4
B1, B2
–
10 to 6
M5
2.7 to 3.0
(23.9 to 26.6)
6
8 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
3.6 Main Circuit Wiring
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
121
3
Electrical Installation