Terminal a2 input signal selection, Terminal a3 analog/ptc input selection – Yaskawa CIMR-AU 200V Drives User Manual
Page 137

n
Using External Power Supply (Sink Mode)
The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between 12
and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.
External Power Supply (V)
Load Impedance (kΩ)
12 to 15 Vdc ±10%
1.0 kΩ or higher
MP
AC
Load Impedance
Sink Current
External Power Supply
Figure 3.33 Pulse Output Connection Using External Voltage Supply
u
Terminal A2 Input Signal Selection
Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained in
. Set parameter H3-09 accordingly as shown in
.
Note:
If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Table 3.14 DIP Switch S1 Settings
Setting
Description
V (left position)
Voltage input (-10 to +10 V or 0 to 10 V)
I (right position)
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table 3.15 Parameter H3-09 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H3-09
Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
u
Terminal A3 Analog/PTC Input Selection
Terminal A3 can be configured either as multi-function analog input or as PTC input for motor thermal overload protection.
Use switch S4 to select the input function as described in
.
Table 3.16 DIP Switch S4 Settings
Setting
Description
AI (lower position) (default)
Analog input for the function selected in parameter H3-06
PTC (upper position)
PTC input. Parameter H3-06 must be set to E (PTC input)
3.8 Control I/O Connections
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
137
3
Electrical Installation