F7: Communication Option Card (SI-EM3, SI-EN3, SI-EP3)
F7 parameters are used for EtherNet/IP, Modbus TCP/IP, and PROFINET options. Other parameters in the F7 group are used
for communication-protocol-specific settings. For more details on a specific option card, refer to the instruction manual for
the option.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F7-01
(03E5)
<1>
IP Address 1
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Range: 0 to 255
–
F7-02
(03E6)
<1>
IP Address 2
IP Address 2
Sets the second most significant octet of network static IP
address.
Default: 168
Range: 0 to 255
–
F7-03
(03E7)
<1>
IP Address 3
IP Address 3
Sets the third most significant octet of network static IP
address.
Default: 1
Range: 0 to 255
–
F7-04
(03E8)
<1>
IP Address 4
IP Address 4
Sets the fourth most significant octet of network static IP
address.
Default: 20
Range: 0 to 255
–
F7-05
(03E9) Subnet Mask 1
Subnet Mask 1
Sets the most significant octet of network static Subnet Mask. Default: 255
Range: 0 to 255
–
F7-06
(03EA) Subnet Mask 2
Subnet Mask 2
Sets the second most significant octet of network static Subnet
Mask.
Default: 255
Range: 0 to 255
–
F7-07
(03EB) Subnet Mask 3
Subnet Mask 3
Sets the third most significant octet of network static Subnet
Mask.
Default: 255
Range: 0 to 255
–
F7-08
(03EC) Subnet Mask 4
Subnet Mask 4
Sets the fourth most significant octet of network static Subnet
Mask.
Default: 0
Range: 0 to 255
–
F7-09
(03ED) Gateway Address 1
Gateway IP Add 1
Sets the most significant octet of network Gateway address.
Default: 192
Range: 0 to 255
–
F7-10
(03EE) Gateway Address 2
Gateway IP Add 2
Sets the second most significant octet of network Gateway
address.
Default: 168
Range: 0 to 255
–
F7-11
(03EF) Gateway Address 3
Gateway IP Add 3
Sets the third most significant octet of network Gateway
address.
Default: 1
Range: 0 to 255
–
F7-12
(03E0) Gateway Address 4
Gateway IP Add 4
Sets the fourth most significant octet of network Gateway
address.
Default: 1
Range: 0 to 255
–
F7-13
(03F1) Address Mode at Startup
IP Add Mode Sel
0: User Defined
1: BOOTP
2: DHCP
Select the option address setting method
0: Static
<2>
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
–
F7-14
(03F2) Duplex Mode Selection
Duplex Select
0: Half Duplex
1: Auto Negotiate
2: Full Duplex
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default: 1
Range: 0 to 2
–
F7-15
(03F3)
Communication Speed
Selection
Baud Rate
10: 10 Mbps
100: 100 Mbps
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
–
F7-16
(03F4)
Communication Loss
Timeout
CommLoss Tout
Sets the timeout value for communication loss detection in
tenths of a second. A value of 0 disables the connection
timeout.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min.: 0
Max.: 300
–
F7-17
(03F5)
EtherNet/IP Speed
Scaling Factor
EN Speed Scale
Sets the scaling factor for the speed monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-18
(03F6)
EtherNet/IP Current
Scaling Factor
EN Current Scale
Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-19
(03F7)
EtherNet/IP Torque
Scaling Factor
EN Torque Scale
Sets the scaling factor for the torque monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
EN Power Scale
Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–