U1 - 12, U1 - 19 – Yaskawa CIMR-AU 200V Drives User Manual

Page 336

background image

No.

(Addr.

Hex)

Name

Description

Analog

Output Level

Unit

U1-11

(004A) Output Terminal Status Output Term Sts

Displays the output terminal status.

U1 - 11=

00000000

Multi-Function

Digital Output

(terminal M1-M2)

Digital Output

(terminal M3-M4)

Digital Output

(terminal M5-M6)

Multi-Function

Multi-Function

Not Used

Fault Relay

(terminal MA-MC closed

MA/MB-MC open)

1

1

1

1

0

No signal output

available

U1-12

(004B) Drive Status

Int Ctl Sts 1

Displays the drive operation status.

U1 - 12=

00000000

During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection

1

1

1

1
1

1

1
1

No signal output

available

U1-13

(004E) Terminal A1 Input Level Term A1 Level

Displays the signal level to analog input terminal A1.

10 V: 100%

(-10 to +10 V)

0.1%

U1-14

(004F) Terminal A2 Input Level Term A2 Level

Displays the signal level to analog input terminal A2.

10 V: 100%

(-10 to +10 V)

0.1%

U1-15

(0050) Terminal A3 Input Level Term A3 Level

Displays the signal level to analog input terminal A3.

10 V: 100%

(-10 to +10 V)

0.1%

U1-16

(0053)

Output Frequency after

Soft Starter

SFS Output

Displays output frequency with ramp time and S-curves. Units

determined by o1-03.

10 V: Max

frequency

(-10 to +10 V)

0.01 Hz

U1-17

(0058) DI-A3 Input Status

DI Opt Status

Displays the reference value input from the DI-A3 option card.

Display will appear in hexadecimal as determined by the digital

card input selection in F3-01.

3FFFF: Set (1 bit) + sign (1 bit) + 16 bit

No signal output

available

U1-18

(0061) oPE Fault Parameter

OPE Error Code

Displays the parameter number that caused the oPE02 or oPE08

operation error.

No signal output

available

U1-19

(0066)

MEMOBUS/Modbus

Error Code

Transmit Err

Displays the contents of a MEMOBUS/Modbus error.

U1 - 19=

00000000

CRC Error
Data Length Error
Not Used

Parity Error
Overrun Error
Framing Error

Timed Out

Not Used

1

1

0

1

1

1

1

0

No signal output

available

U1-21

(0077)

AI-A3 Terminal V1

Input Voltage Monitor

AI Opt Ch1 Level

Displays the input voltage to terminal V1 on analog input card

AI-A3.

10 V: 100%

(-10 to +10 V)

0.1%

U1-22

(072A)

AI-A3 Terminal V2

Input Voltage Monitor

AI Opt Ch2 Level

Displays the input voltage to terminal V2 on analog input card

AI-A3.

10 V: 100%

(-10 to +10 V)

0.1%

U1-23

(072B)

AI-A3 Terminal V3

Input Voltage Monitor

AI Opt Ch3 Level

Displays the input voltage to terminal V3 on analog input card

AI-A3.

10 V: 100%

(-10 to +10 V)

0.1%

U1-24

(007D) Input Pulse Monitor

Term RP Inp Freq

Displays the frequency to pulse train input terminal RP.

Determined by

H6-02

1 Hz

B.13 U: Monitors

336