beautypg.com

Appendix c - updating controllers & modules, Updating controller & e-bus module software, 87 vcc-x operator interface sd – Orion System VCC-X Controller User Manual

Page 87

background image

APPENDIX C - UPDATING CONTROLLERS & MODULES

87

VCC-X Operator Interface SD

Updating Controller & E-BUS Module Software

E-BUS Modules

1. Press

<2>

to update an E-BUS Module.

The following screen will appear:

Enter Board Address

0

Esc) Exit Menu

2. Enter the address of the E-BUS module you are updating

and then press

. The following is the list of

Module addresses:

MHGRV-X - address 132

MODGAS-X - address 138

PREHEAT-X - address 157

RSMV #1 - address 152
RSMV #2 - address 153
RSMV #3 - address 154
RSMV #4 - address 155
WSHP-X - address 17

3 The

Software Version Screen will appear as shown

below. Enter

<0>

for the latest software version or enter

the number of an older version if given to you by
Technical Support. Then press

.

Software Version
Enter 0 for Latest

0

Esc) Exit Menu

4. The screen will display the following messages:
“Resetting

Unit”

“Load Sys Info”

5. If communications are successful, the screen will

display, the name of the HEX fi le on the top line,
“Flash Memory Erased” on the second line, and the
progress percentage on the third line.

NOTE:

If communications are not successful, the screen

will display, “Press Any Key to Continue. Cannot Load
Sys Info.” Make sure you have the right address and the
right software version on your SD card. If these two
items are correct and you still experience a problem,
contact Technical Support.

6. When updating is complete, the screen will display,

“Finish Download.”