beautypg.com

Rsmv configuration, Rsmv confi guration screens, Vcc-x operator interface sd 66 – Orion System VCC-X Controller User Manual

Page 66: Rsmv compressor settings screens

background image

RSMV CONFIGURATION

VCC-X Operator Interface SD

66

RSMV Confi guration Screens

SETUP RSM STAGING
COMPRESSOR SETTINGS

RSMV Compressor Settings Screens

From the screen below, select “ Compressor Settings” and press

.

Setpoint Screen #1 - RSM #1 OAT Lockout

RSM 1 OAT LOCKOUT

Comp A1: 50ºF
Comp A2: 50ºF

The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.

Description

Minimum

Default

Maximum

OAT Lockout
Compressor Cooling

-30ºF

(-34.4

º

C)

50ºF

(10

º

C)

100ºF

(37.7

º

C)

The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.

Description

Minimum

Default

Maximum

OAT Lockout
Compressor Cooling

-30ºF

(-34.4

º

C)

50ºF

(10

º

C)

100ºF

(37.7

º

C)

RSM 2 OAT LOCKOUT

Comp B1: 50ºF
Comp B2: 50ºF

Setpoint Screen #2 - RSM #2 OAT Lockout

The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.

Description

Minimum

Default

Maximum

OAT Lockout
Compressor Cooling

-30ºF

(-34.4

º

C)

50ºF

(10

º

C)

100ºF

(37.7

º

C)

RSM 3 OAT LOCKOUT

Comp C1: 50ºF
Comp C2: 50ºF

Setpoint Screen #3 - RSM #3 OAT Lockout

The RSM will Lockout Compressor (Mechanical) Cooling when the
Outdoor Air Temperature is below this Compressor Cool Lockout
Setpoint.

Description

Minimum

Default

Maximum

OAT Lockout
Compressor Cooling

-30ºF

(-34.4

º

C)

50ºF

(10

º

C)

100ºF

(37.7

º

C)

RSM 4 OAT LOCKOUT

Comp D1: 50ºF
Comp D2: 50ºF

Setpoint Screen #4 - RSM #4 OAT Lockout

Setpoint Screen #5 - Mod Cool Reset Position

& Deadband

MOD COOLING RESET

Position: 30%

Deadband: 5.0ºF

If the VFD compressor in a tandem circuit has reached 100% for the
Stage Up Delay period and the next compressor is staged on, this
screen allows you to confi gure the position (capacity) that the VFD
compressor(s) will initially start at once the next compressor stages
on. If the Supply Air Temperature is above the Cooling Supply Air
Setpoint plus the Mod Cool Deadband (confi gured in this screen)
when the fi xed compressor stages on, the VFD compressor will start
at 100% and modulate down as needed to maintain the Cooling Sup-
ply Air Setpoint. If the Supply Air Temperature is above the Cooling
Supply Air Temperature by less than this deadband amount, then
the VFD compressor will go to the Mod Cool Position (confi gured
in this screen) and modulate from there as needed to maintain the
Cooling Supply Air Setpoint.

Description

Minimum

Default

Maximum

Mod Cool Position

0%

30%

100%

Mod Cool Deadband

0.0ºF

(-17.7

º

C)

5.0ºF

(1.00

º

C)

30.0ºF

(-1.11

º

C)