VCC-X Operator Interface SD

VCC-X CONFIGURATION

25

Confi guration Screens

In order to correctly set up the VCC-X Controller, you must fi rst
confi gure several parameters in regard to the type of HVAC unit
and system you have installed. Most of these values and operat-
ing parameters are only set once at the initial system setup and are
never changed.

Modular Service Tool Instructions

No matter what screen or menu you’re in, press

TION>

. The Unit Selection Screen will appear, shown below, request-

ing that you enter the unit ID number.

VCC-X CONFIGURATION
RSM CONFIGURATION

Select & Press Enter

Enter

the correct unit ID number of the VCC-X Controller you want

to confi gure and then press

. Once communication is es-

tablished, the *00* message will go away. Then

press

<

>

. Select

VCC-X Confi guration and then press

. Press

to save entered data and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

System Manager SD Instructions

From any Main screen, press

. The screen below

will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will
be displayed.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter

the correct unit ID number of the VCC-X Controller you

want to confi gure and then press

. Once communication

is established, the *00* message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

The following screen will be displayed:

Change Setpoints
Configure Unit
Save/Copy/Restore

VCC-X CONFIGURATION
RSM CONFIGURATION

Select & Press Enter

On the fi rst screen, scroll down to the ‘Confi gure Unit’ option and
press

. On the second screen, select VCC-X Confi guration

and then press

. This will take you to the fi rst Confi gura-

tion Screen shown below.

Confi guration Screen #1 - Sensor Scaling

VCC-X Cnfg ID #

Sensor Scaling

Fahrenheit

USE < or > TO CHANGE

Options are Fahrenheit or Celsius. If you make a change to this
screen, after you press

to have the system accept the

change, you must return to the Unit Selection Screen to re-establish
communications with the Controller. Default is Fahrenheit.

Confi guration Screen #2 - RSM #1 & #2

Module Installed

VCC-X Cnfg ID #
RSM#1 Installed: NO
RSM#2 Installed: NO

USE < or > TO CHANGE

If you have a one RSMV Module installed, the 1st confi guration op-
tion should be confi gured as YES. If you have a 2nd RSMV Module
installed, the 2nd confi guration option should be confi gured as YES.
Default is NO.

VCC-X Confi guration Screens

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down