VCC-X STATUS

59

Status Screen #18 - Economizer Enabled and

Economizer Position

VCC-X v1.02 ID #

Economizer

Enabled: YES/NO

Position: XXX%

Line 3 Economizer Enabled

This line will display YES if the Economizer is enabled

and NO if the Economizer is not enabled. The

Economizer is enabled whenever the Economizer Enable

Temperature (options: Drybulb, Wetbulb or Dewpoint)

is below the Economizer Enable Setpoint.

Line 4 Current Economizer Open Percentage

This shows the percentage signal currently being sent to

the Economizer (Outdoor Air Damper), whether the unit

is

confi gured for Economizer Control or simply has a

Minimum Outdoor Air Damper position confi gured. If

Economizer Control is not confi gured, it will display

0%.

Status Screen #19 - Title 24 Economizer

Feedback

VCC-X v1.02 ID #

Economizer

Feedback: XXX%

[Only For Title 24]

Line 3 Title 24 Economizer Open Percentage

If

confi gured for Title 24 Economizer operation, this

shows the Outdoor Air Damper Feedback Signal

percentage. If Title 24 Economizer Control is not

confi gured, it will display 0%.

Status Screen #20 - Economizer in IAQ Mode

and Minimum Economizer Position

VCC-X v1.02 ID #

Econo in IAQ Mode

YES/NO

Econo Min Pos: XXX%

Line 3 Economizer in IAQ Mode

This line will display YES if the Economizer (OA)

Minimum Damper Position has been overridden based

on

CO

2

IAQ operation.

Line 4 Economizer Minimum Percentage

This shows the current Economizer (OA) Minimum

Damper Position. If the unit is not in IAQ Mode, this

will be the regular confi gured Minimum Damper

Position. If the unit is in IAQ Mode, this will show the

re-calculated Minimum Damper Position.

Status Screen #21 - CO

2

Level and Setpoints

VCC-X v1.02 ID #

CO2 Level: XXXXppm
Min Setpt: XXXXppm
Max Setpt: XXXXppm

Line 2 Current CO

2

Level

Indicates

the

CO

2

Level. You must install and confi gure a

CO

2

Sensor to display the CO

2

Level. If a CO

2

Sensor is

not installed and confi gured, this line will display 0

PPM.

Line 3 Minimum CO

2

Setpoint

This is the Minimum CO

2

Setpoint that was confi gured

in

Setpoint Screen #28.

Line 4 Maximum CO

2

Setpoint

This is the Maximum CO

2

Setpoint that was confi gured

in

Setpoint Screen #28.

Status Screen #22 - Outdoor Air CFM & Supply

Air CFM

VCC-X v1.02 ID #

Outdoor kCFM: XXX.XX
Supply kCFM: XXX.XX

Line 2 Outdoor Air CFM

If an Outdoor Air airfl ow monitoring station is being

used, this is the current CFM reading of that device.

K

=

1000

Line 3 Supply Air CFM

If a Supply Air airfl ow monitoring station is being used,

this is the current CFM reading of that device.

K = 1000