beautypg.com

Vcc-x setpoints, Vcc-x setpoint screens, Vcc-x operator interface sd 48 – Orion System VCC-X Controller User Manual

Page 48

background image

VCC-X SETPOINTS

VCC-X Operator Interface SD

48

Setpoint Screen #27 - Economizer Maximum

Position in High CO

2

Level

VCC-X Spts ID:#

Econo Max Pos In

High CO2.: 50%

This Setpoint allows you to set the Maximum Position the Econo-
mizer will open if high CO

2

conditions occur in the space. The

Maximum Economizer Position Setpoint is used to limit the amount
of Outdoor Air that will be introduced to the HVAC unit in order to
ensure the unit is operating within its Heating and Cooling design
limitations. As shown in the table that follows, the Minimum setting
for this Setpoint is the value previously set for the Economizer Min
Position Setpoint.

CO

2

override cannot be used in conjunction with airfl ow control of

the Outdoor Air damper (previous screen) in this version.

Description

Minimum

Default

Maximum

Maximum Economizer
Position In High CO

2

Economizer

Min Position

50%

100%

Setpoint Screen #28 - CO

2

Setpoints Min/Max

VCC-X Spts ID:#

CO2 Setpoints

Min CO2: 900ppm
Max CO2: 1000ppm

The Min CO

2

Setpoint is the threshold CO

2

level at which the Econo-

mizer Min Damper Position (Setpoint Screen #24) will begin to be
reset higher. The Max CO

2

Setpoint is the CO

2

level at which the

Economizer Min Damper Position will be reset to the Econo Max
Pos In High CO

2

(Setpoint Screen #27). In between those CO

2

lev-

els, the Economizer Minimum Position will be proportionally reset
between the values set in Setpoint Screens #24 and #27.

Description

Minimum

Default

Maximum

Minimum CO

2

Level

0 PPM

900 PPM

2000 PPM

Maximum CO

2

Level

0 PPM

1000 PPM

2000 PPM

Setpoint Screen #29 - CO

2

Altitude Setpoint

VCC-X Spts ID:#

Altitude

Setpoint: 1000ft

Enter the distance above sea level for the installed CO

2

Sensor. Altitude

correction is required for valid readings if you are above 500 feet. High
limit = 15,000 feet; Low limit = 0 feet.

Description

Minimum

Default

Maximum

Altitude Setpoint

0 Feet

1000 Ft.

15,000 Ft.

Setpoint Screen #30 - Building Pressure

Setpoint & Deadband

VCC-X Spts ID:#

Building Pressure

Setpoint: 0.02”
Deadband: 0.01”

The VCC-X can maintain Building Static Pressure anytime the
Supply Fan is operating. A Building Pressure Transducer must be
connected to the VCC-X. The following are the available control
options.

Direct Acting Building Pressure Control

On/Off Exhaust Fan

—If an On/Off Exhaust Fan is

being used, a relay output must be confi gured for

“Exhaust Fan”. This relay will energize whenever the

Building Pressure rises above the Building Pressure

Setpoint by the Deadband amount. The relay will de-

energize when the Building Pressure falls below the

Building Pressure Setpoint by the Deadband amount.

Exhaust Fan VFD or Modulating Exhaust

Damper

—If confi gured for Modulating Exhaust, a user-

adjustable voltage output (AOUT4 – Building Pressure

Output on the VCC-X) will be used to control this fan or

damper. An Exhaust Relay can be confi gured if

necessary to enable the fan or damper. Whenever the

Building Pressure rises above the Building Pressure

Setpoint by the Deadband amount, the Exhaust Fan

Relay will energize and the Modulating Signal will

activate to control to the Building Pressure Setpoint. If

the Building Pressure falls below the Building Pressure

Setpoint by the Deadband amount, the Modulating

Signal will modulate towards 0% as it attempts to

maintain the Building Pressure Setpoint. The Exhaust

Fan Relay remains energized as long as the Modulating

Signal is above 0%.

VCC-X Setpoint Screens