Vcc-x status, Vcc-x status screens, Vcc-x operator interface sd 58 – Orion System VCC-X Controller User Manual

Page 58

background image

Zone

Zone

VCC-X STATUS

VCC-X Operator Interface SD

58

VCC-X Status Screens

Status Screen #14 - PREHEAT-X Controller

Current Leaving Air and Entering Air

Temperature

VCC-X v1.02 ID #

Preheat-X Temps

Leaving Air: 0.0ºF
Entring Air: 0.0ºF

Line 3 Current PREHEAT-X Leaving Air Temperature

If the Preheat-X Controller (and the associated Leaving

Air Temperature Sensors) is installed and confi gured,

this line will display the current Preheat-X Leaving Air

Temperature.

Line 4 Current PREHEAT-X Entering Air Temperature

If the Preheat-X Controller (and the associated Entering

Air Temperature Sensor) is installed and confi gured, this

line will display the current Preheat-X Entering Air

Temperature.

Status Screen #15 - PREHEAT-X Controller

Modulating Position and Active Stages

VCC-X v1.02 ID #

Preheat-X Status

Mod Pos: XXX%
Active Stages: X

Line 3 Current PREHEAT-X Modulating Position

If you have a PREHEAT-X Controller connected to

the VCC-X Controller and are using Modulating Heat,

this is the current modulating heat signal

.

Line 4 Current PREHEAT-X Active Stages

If you have a PREHEAT-X Controller connected to the

VCC-X Controller, and are using staged heat, this is the

number of stages currently active.

Status Screen #16 - OA Drybulb and Humidity

VCC-X v1.02 ID #

Outdoor Conditions

Drybulb: 0.0ºF

Humidity:

XXX%

Line 3 Current Outdoor Air Drybulb

If an E-BUS Outdoor Air Temperature/Humidity Sensor

has been installed and confi gured on the VCC-X, the

current Outdoor Air Temperature will display on this

line. If the sensor fails, this line will display a

temperature that is half way between the Cooling and

Heating

Lockout

Setpoints.

Line 4 Current Outdoor Air Relative Humidity

If an E-BUS Outdoor Air Temperature/Humidity Sensor

has been installed and confi gured on the VCC-X, the

Outdoor Air Relative Humidity Percentage will appear

on this line. If not, this line will display 0%.

Status Screen #17 - OA Wetbulb and Dewpoint

VCC-X v1.02 ID #

Outdoor Conditions

Wetbulb: 0.0ºF
Dewpoint: 0.0ºF

Line 3 Current Wetbulb Temperature

If an E-BUS Outdoor Air Temperature/Humidity Sensor

has been installed and confi gured on the unit, this line

will display the calculated Outdoor Air Wetbulb

Temperature. If not, it will display 0°F.

Line 4 Current Calculated Outdoor Air Dewpoint
Temperature

If an E-BUS Outdoor Air Temperature/Humidity Sensor

has been installed and confi gured on the unit, the

calculated Outdoor Air Dewpoint Temperature will

appear on this line. If not, this screen displays 0°F.