Orion System Water Source Heat Pump Module Tulsa User Manual
Water source heat pump module technical guide, Factory packaged controls tulsa
Water Source
Heat Pump Module
Technical Guide
WattMaster Label
#LB102069-A
Rev.: 1B
E-BUS
Connector
E-BUS
Connector
+5V
PRES
GND
+24
VA
C
GND
BIN 1
BIN 2
BIN 3
BIN 4
BIN 5
BIN 6
BIN 7
COM
SUCTION
PRESSURE
TRANSDUCERS
#1 thru #4
COMP. 1 ENABLE
COMP. 2 ENABLE
COMP. 3 ENABLE
WSHP Protection Module
Orion No.: OE334-23-WPM
COMP. 4 ENABLE
HEAT ENABLE
H2O POF #1
H2O POF #2
COMMON
T 1
T 2
GND
LEAVING WATER TEMP 1
GROUND
LEAVING WATER TEMP 2
LED BLINK CODES
LED NAME
STATUS
OFF MODE
1
COOLING MODE
2
HEATING MODE
3
LED NAME
ALARM
LOW SUCTION PRESSURE
1
COMPRESSOR LOCKOUT
2
WATER FLOW FAILURE
3
LOW LEAVING WATER TEMP.
4
LED NAME
PRES 1-4
SENSOR DETECTED
ON
NO SENSOR DETECTED
OFF
LOW SUCTION PRESSURE
1
COMPRESSOR LOCKOUT
2
AO1
A 2
O
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP. #2 ENABLE
COMP. #1 ENABLE
R1
R2
R3
R4
RC
RELAY COMMON
COMP. #3 ENABLE
COMP. #4 ENABLE
SYSTEM A - CNTRLR C2
SYSTEM B - CNTRLR C2
+5V
PRES
GND
NOT USED
DIGITAL COMP #1 THRU #4
NON-DIGITAL COMP #1 THRU #4
COPELAND CNTRLR P6
COPELAND CNTRLR P5
AAON No.: R90680
WattMaster Label
#LB102069-A
Rev.: 1F
E-BUS
Connector
E-BUS
Connector
+24
VA
C
GND
BIN 1
BIN 2
BIN 3
BIN 4
BIN 5
BIN 6
BIN 7
COM
COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
WSHP Module
Orion No.: OE334-23-WPM-A
AAON No.: R88350
www.aaon.com
www.orioncontrols.com
COMP. B2 ENABLE
HEAT ENABLE
WATER POF A
WATER POF B
COMMON
T 1
T 2
GND
LEAVING WATER TEMP A
GROUND
LEAVING WATER TEMP B
LED BLINK CODES
LED NAME
STATUS
OFF MODE
1
COOLING MODE
2
HEATING MODE
3
LED NAME
ALARM
LOW SUCTION PRESSURE
1
COMPRESSOR LOCKOUT
2
WATER FLOW FAILURE
3
LOW LEAVING WATER TEMP.
4
LED NAME
PRES 1-4
SENSOR DETECTED
ON
NO SENSOR DETECTED
OFF
LOW SUCTION PRESSURE
1
COMPRESSOR LOCKOUT
2
AO1
A 2
O
STAGE 1- COMP. A1/B1-
STAGE 2 - COMP. A2/B2
DIGITAL COMP. A1, A2, B1, B2
RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC
COMP. A2 ENABLE
COMP. A1 ENABLE
R1
R2
R3
R4
R5
RC
RELAY COMMON
COMP. B1 ENABLE
COMP. B2 ENABLE
ALARM OUTPUT
CONNECT TO CNTLR C2 TERM.
+5V
PRES
GND
+5V
PRES
GND
SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2
+5 NOT USED, PRES TO P6 & GND TO P5
+5 TO RED, PRES TO WHT & GND TO BLK
DIGITAL COMRESSORS
NON-DIGITAL COMPRESSORS
LW: 36ºF HSP: 100 PSIG
Factory Packaged Controls
Tulsa