VCC-X CONFIGURATION

VCC-X Operator Interface SD

30

VCC-X Confi guration Screens

Confi guration Screen #27 - Mechanical Heat/

Cool Alarm Delay

VCC-X Cnfg ID #

Mech Heat/Cool

Alarm Delay: 15Min

Enter a time delay between 0-240 minutes for a delay in the time that
it takes an alarm to be generated.

When Heating or Cooling Mode is

initiated and staging is activated, if the Supply Air Temperature does
not rise or fall 5°F within this time period, a Mechanical Heating
or Cooling failure alarm will be generated. The Alarm is for Status
Reporting only. The HVAC unit will continue to run. This alarm
does not apply if Modulating Cooling or Heating are confi gured.
Default is 15 minutes.

Description

Minimum

Default

Maximum

Mechanical Heat/Cool
Failure Alarm Delay

0 Min

15 Min

240 Min

Confi guration Screen #28 - Economizer Control

Type

VCC-X Cnfg ID #

Econo Control Type

No Economizer

USE < or > TO CHANGE

Default is No Economizer. Available options are:

No Economizer

Standard Economizer

IAQ Economizer (Economizer with CO

2

Override)

Confi guration Screen #29 - Title 24 Economizer

VCC-X Cnfg ID #

Title 24

Economizer: NO

USE < or > TO CHANGE

If this unit has Title 24 Economizer operation, this option should be
confi gured as YES. Default is NO.

Confi guration Screen #30 - Economizer in

Unoccupied Mode

VCC-X Cnfg ID #

Econo Control In

Unoc Mode: NO

USE < or > TO CHANGE

Select

YES for the Economizer to operate in the Unoccupied Cooling

Mode. Default is NO.

NO

You want the Economizer to always remain fully

Closed in the Unoccupied mode.

YES

You want to use the Economizer as necessary

during Unoccupied Night Setback cooling calls. It will

be utilized just as it would be in the Occupied mode with

the same outdoor enable temperature. If not being used

for Night Setback Free Cooling, the Economizer will be

closed.

Confi guration Screen #31 - Economizer Enable

Source

VCC-X Cnfg ID #

Econo Enable Source

Drybulb

USE < or > TO CHANGE

This confi guration option is available if the unit was confi gured for
Economizer Control.

Default is Drybulb. Available options are:

Drybulb

If the Outdoor Air Drybulb temperature is

below the Economizer Enable Setpoint, the Economizer

can be used as the fi rst stage of cooling.

Wetbulb (OA RH Sensor needed)

If the Outside Air

Wetbulb temperature is below the Economizer Enable

Setpoint, the Economizer can be used as the fi rst stage of

cooling.

Dewpoint (OA RH Sensor needed)

If the Outdoor

Air Dewpoint temperature is below the Economizer

Enable Setpoint, the Economizer can be used as the fi rst

stage of cooling.

Confi guration Screen #32 - Economizer Control

Loop Rate

VCC-X Cnfg ID #

Economizer Control

Rate: 10 s

[ 1 - 30 Seconds ]

Enter

a number between 1 and 30 seconds. This is the time period

between changes to the Economizer position. Default is 10 seconds.