VCC-X STATUS

61

Status Screen #27 - Return Air Damper Signal

& Return Air Bypass Damper Signal

VCC-X v2.00 ID 101

Return Dmper: XXX%
Bypass Dmper: XXX%

[Optional Outputs]

Line 2 Current Return Air Damper Signal

If confi gured for Return Air Bypass Control, this

indicates the current Output Signal percentage being

sent to the Return Air Damper Actuator. If you haven’t

confi gured a Return Air Bypass Damper, [No Return

Dmp Confg] will be displayed instead.

Line 3 Current Return Air Bypass Damper Signal

If confi gured for Return Air Bypass Control, this

indicates the current Output Signal percentage being

sent to the Return Air Bypass Damper Actuator. If you

haven’t

confi gured a Return Air Bypass Damper, [No

Bypass Dmp Confg] will be displayed instead.

Line 4 Indicates That These Are Optional Outputs

This output may or may not have live data to display.

Status Screen #28 - Reset Voltage Signal

VCC-X v2.00 ID 101

Reset Voltage Signal

0.0VDC

Line 2-3 Reset Voltage Signal

If using a Remote Voltage Signal to reset the Supply Air

Temperature setpoint, this screen will display the current

Reset Voltage Signal being sent to the Controller.

VCC-X Status Screens

Status Screens #29-#36 - VCC-X Relays

VCC-X v1.02 ID #

On Board Rly 1-8

FAN

ON/OFF

Line 2 On Board Relays 1-8 Status

Line 3 Current description of what this Relay is

confi gured for

On screen 29, this line will display FAN.

On screens 30-36, this line will indicate the relay’s use.

Possible options are:

Not Used (Default)

Cool

Stage

Heat

Stage

Mod

Heat

Enable

Mod Cool Enable

Warmup

/

Cooldown

ReHeat

PreHeat

Low

Ambient

Exhaust

Fan

Economizer

Heat

Wheel

Occupied

Mode

Override

Mode

Alarm

Active

Line 4 Current Relay Status

This line will display the ON/OFF condition for that

relay. FORCED ON or FORCED OFF will appear if

this Relay is in a Force Mode. Possible options are as

follows:

ON OFF

FORCED

ON

FORCED

OFF