System Manager SD Keys and Buttons

Operator Interfaces

In order to confi gure and program the Orion System controllers,
you must have an Operator’s Interface or a personal computer with
the Prism 2 computer front-end software installed. Three different
Operator Interfaces are available for programming of the Orion
Controls System—the Modular Service Tool SD, the Modular Sys-
tem Manager SD, and/or the System Manager TS II. These devices
allow you to access the status and setpoints of the controllers on your
communications loop. This manual describes the Modular System
Manager SD. If using the System Manager TS II, please see the
System Manager TS II Technical Guide. If using Prism 2, please see
the Prism 2 Technical Guide.

The Modular System Manager SD allows you to view any input or
output status and change any setpoint to fi ne-tune the operations of the
total system. All keypad operations are simple and straightforward,
utilizing non-cryptic plain English messages.

Display Screens & Data Entry Keys

See the chart below for a list of the keypad descriptions and functions.

Keypad

Description

Function

ESC

Use this key to exit from screens or from data

entry or to return to the Main Screen from

any screen in the system.

ENTER

Use this key to enter a new value.

Clear

If a data entry mistake is made, press this key

to clear the data entry fi eld and start over.

Minus

If a setpoint with a negative value is required,

press this key for the minus sign.

DEC

Press this key when entering data that re-

quires a decimal point.



Use these keys to change values in the Con-

fi guration Screens as prompted.


Use these keys to step backward or forward

through the screens.

Mode Selection Buttons

The Modular System Manager is provided with “Mode Selection
Buttons.” These buttons give you instant access to the specifi c mode
desired without having to scroll through several menu screens to
get there.

Button

Description

Function

STATUS

Pressing this button takes you directly to

the controller “Status” screens.

SETPOINTS

Pressing this button takes you directly to

the controller “Setpoints” screens and

“Confi guration” menu.

SCHEDULES

Pressing this button takes you directly to

the controller “Schedules” screens.

OVERRIDES

Pressing this button takes you directly to

the controller “Overrides” screen. See the

“Override Button” section on page 21 for a

description of this function.

See Notes 1 & 2 below.

ALARMS

Pressing this button takes you directly to

the controller “Alarms” screen. See the

“Alarms Button” section on page 20 for a

description of this function.

See Notes 1 & 2 below.

NOTES:

(1) This button only functions when the system is confi gured for
“Network Mode” or “Multiple MGRS Mode.” It will not function
in “Stand Alone Mode.”

(2) The “Search for Units” function must be performed on the System
Manager upon initial system setup before this function will be avail-
able. See the “Network Mode & Multiple Managers Loop Search”
on page 20 of this manual for complete instructions on performing
a loop search.

Table 3: Keypad Descriptions