Zone

Zone

VCC-X STATUS

VCC-X Operator Interface SD

60

Status Screen #23 - Return Air CFM & Exhaust

Air CFM

VCC-X v1.02 ID #

Return kCFM: XXX.XX
Exhaust kCFM: XXX.XX

Line 2 Return Air CFM

If a Return Air airfl ow monitoring station is being used,

this is the current CFM reading of that device. K = 1000

Line 3 Exhaust Air CFM

If an Exhaust Air airfl ow monitoring station is being

used, this is the current CFM reading of that device.

K = 1000

Status Screen #24 - Duct Static Pressure

Setpoint & Output %

VCC-X v1.02 ID #

Static Pr: X.XX”
Setpoint: X.XX”
Output: XXX%

Line 2 Current Duct Static Pressure

Requires the installation and wiring of a Duct Static

Pressure Sensor. If you do not have a Duct Static

Pressure Sensor correctly installed and wired to the

controller, this line will display “0.0”.

Line 3 Duct Static Pressure Setpoint

This is the Duct Static Pressure Setpoint confi gured in

Setpoint Screen #12.

Line 4 Current Duct Static Pressure Output Signal
Percentage

Indicates the output signal percentage being supplied to

the VFD Supply Fan or Bypass Damper Actuator when

you have confi gured one of these options for your

HVAC

unit.

If you have not confi gured Duct Static Pressure Control,

this line will display [No Press Out Confg].

Status Screen #25 - Building Pressure & Set-

point

VCC-X v1.02 ID #

Building Pressure

Pressure:

XXX”

Setpoint:

X.XX”

Line 3 Current Building Pressure

Indicates the current Building Pressure. This display

requires the installation of a Building Pressure Sensor.

If you don’t have a Building Pressure Sensor correctly

installed and wired to the controller, this line will

display

“0.0”.

Line 4 Building Pressure Setpoint

This is the Building Static Pressure Setpoint confi gured

in

Setpoint Screen #30.

If you have not confi gured Building Pressure Control,

this line will display [No Press Out Confg].

Status Screen #26 - Building Pressure Exhaust

Fan and Output %

VCC-X v1.02 ID #

Building Pressure

Exhaust Fan: ON/OFF
Output: XXX%

Line 3 Building Pressure Exhaust Fan Status

Indicates whether the Exhaust Fan Relay is On or Off.

Line 4 Current Building Pressure Output Signal Percentage

Indicates the output signal percentage being supplied to

the building pressure control fan or damper. For Direct

Acting control, this would be to an Exhaust Fan VFD or

a Modulating Exhaust Damper. For Reverse Acting

control, this would be to the Outdoor Air Damper or

Supply

Fan

VFD.

If you have not confi gured Building Pressure Control,

this line will display [No Press Out Confg].

VCC-X Status Screens