VCC-X Operator Interface SD

VCC-X SETPOINTS

51

VCC-X Setpoint Screens

Setpoint Screen #40 - Return Air Bypass

Damper Factor Setpoint

VCC-X Spts ID:#

Return Air Bypass

Damper Factor

Setpoint: 40%

This setpoint is used when you have an EM1 Expansion Module
installed and confi gured for Return Air Bypass Damper control. The
Return Air Bypass Damper Factor Setpoint is a percentage value
that is used to calculate the Return Air Damper position in relation
to the Return Air Bypass Damper position. This provides a method
for adjusting the airfl ow through the Return Air Bypass Damper.

Increasing this percentage increases the airfl ow through the Return
Air Bypass Damper by causing the Return Air Damper to move fur-
ther towards its closed position in relation to the Return Air Bypass
Damper moving towards its open position.

Description

Minimum

Default

Maximum

Damper Factor

0%

40%

100%

Setpoint Screen #41 - Warm-Up Supply Air

Temperature Setpoint

VCC-X Spts ID:#

Warmup Supply Air

Setpoint: 100.0ºF

Heating will be controlled to this Supply Air Setpoint during Morn-
ing Warm-Up.

Description

Minimum

Default

Maximum

Warm-Up SAT Setpoint

40ºF

(4.44

º

C)

100ºF

(37.78

º

C)

240ºF

(115.56

º

C)

Setpoint Screen #42 - Cool-Down Supply Air

Temperature Setpoint

VCC-X Spts ID:#

Cooldown Supply Air

Setpoint: 55.0ºF

Cooling will be controlled to this Supply Air Setpoint during Cool-
Down.

Description

Minimum

Default

Maximum

Cool-Down SAT Setpoint

30ºF

(-1.11

º

C)

55ºF

(12.78

º

C)

80ºF

(26.67

º

C)

Setpoint Screen #43 - PREHEAT-X Cool Mode

and Heat Mode Setpoints

VCC-X Spts ID:#

Preheat-X Spts

Cool Mode: 40.0ºF

Heat Mode: 60.0ºF

If using the Preheat-X Controller with the VCC-X, this screen al-
lows you to set the Preheat setpoint you want to control to during
the Cooling and the Heating Modes.

Description

Minimum

Default

Maximum

Preheat-X Cool Mode
Setpoint

35.0ºF

(1.66

º

C)

40.0ºF

(4.5

º

C)

90.0ºF

(32.2

º

C)

Preheat-X Heat Mode
Setpoint

35.0ºF

(1.66

º

C)

60.0ºF

(15.5

º

C)

90.0ºF

(32.2

º

C)

Setpoint Screen #44 - PREHEAT-X Vent Mode

Setpoint

VCC-X Spts ID:#

Preheat-X Spts

Vent Mode: 50.0ºF

If using the Preheat-X Controller with the VCC-X, this screen al-
lows you to set the Preheat setpoint you want to control to during
the Vent Mode.

Description

Minimum

Default

Maximum

Preheat-X Vent Mode
Setpoint

35.0ºF

(1.66

º

C)

50.0ºF

(10.0

º

C)

90.0ºF

(32.2

º

C)

Setpoint Screen #45 - Superheat Setpoint

VCC-X Spts ID:#

Superheat

Setpoint: 15ºF

The Superheat Setpoint is the target Superheat used by the Refriger-
ant Module to correctly drive the EXV valves.

Description

Minimum

Default

Maximum

Superheat Setpoint

1ºF

(-17.2

º

C)

15ºF

(-16.9

º

C)

30ºF

(-1.11

º

C)