VAV/ZONE CONFIGURATION

VCC-X Operator Interface SD

70

VAV/Zone Confi guration Screens

Confi guration Screen #3 - Voting Zone

XX Box Cnfg IDXXXX

Is This Box a

Voting Zone..: YES

Use < Or > To Change

If this is a Zoned System, select YES so that the box can be included
as a voting zone.

Confi guration Screen #4 - Pressure

Independent Airfl ow Constant

XX Box Cnfg IDXXXX

Pr Independent Boxes

Airflow @ 1” WG

Constant..: 1200 CFM

If this is a Pressure Independent Box, you must enter this airfl ow
constant so that the CFM readings can be correctly calculated. This
airfl ow constant is provided by the box manufacturer and depends
on the diameter of the duct.

Confi guration Screen #5 - Expansion Relays

Heating Stages

XX Box Cnfg IDXXXX

Expansion Relays

[Optional]

Steps of Reheat.: 2

If you require the VAV/Zone Controller to control reheat for the zone
it is installed in, you must include a relay expansion board and then
confi gure the number of heating stages (1, 2, or 3) that it will be
controlling whenever there is a heating demand in the space. Enter

<0>

if you don’t require this option.

Confi guration Screen #6 - Proportional

Heating Signal

XX Box Cnfg IDXXXX

Proportional Heating
Signal..: 0 - 10 VDC
Use < Or > To Change

Select 0-10 VDC or 2-10 VDC as the range of the proportional heat
output.

Confi guration Screen #7 - Box Heat Allow

XX Box Cnfg IDXXXX
Allow Box Heat With

HVAC Heat....: NO

Use < Or > To Change

Select YES to allow the Heating Relay’s Controlling Box Heat to
remain on even when the HVAC unit is in Supply Air Heating Mode.
This is used as a method to provide supplemental heat if for some
reason the HVAC heat cannot satisfy the heating demand.

Confi guration Screen #8 - Main Fan Status

XX Box Cnfg IDXXXX

This Unit Needs Main

Fan Status...: NO

Use < Or > To Change

This setting only applies to the unoccupied mode of operation. Select
YES to activate the heating stages only when the main fan is operat-
ing on non-fan terminal units. For series fan terminal units, if this
setting is set to YES, the series box fan will only run when the main
HVAC unit fan is running or when a space heating demand is made.
For series fan terminal units, if this setting is set to NO, the series
box fan will only run when a space heating demand is made. This
setting has no effect on the parallel fl ow fan terminal unit.