Vcc-x setpoints, Vcc-x setpoint screens, Vcc-x operator interface sd – Orion System VCC-X Controller User Manual

Page 53

background image

VCC-X Operator Interface SD

VCC-X SETPOINTS

53

Setpoint Screen #49 - OAT Sensor Calibration

- Current and Offset

VCC-X Spts ID:#

OAT Sensor Cal

Current: 0.0ºF
Offset.: 0.0ºF

If the Outdoor Air Temperature Sensor is reading incorrectly, you
can use this option to enter an offset temperature to adjust the
Sensor’s Temperature. Line 3 will display the current Outdoor Air
Temperature Sensor Reading. Enter a positive Sensor Calibration
value in Line 4 to raise the Outdoor Air Temperature Sensor reading
or a negative value in Line 4 to lower the Sensor reading.

Description

Minimum

Default

Maximum

OAT Sensor Calibration

Offset

-100.0ºF

(-55.5

º

C)

0.0ºF
(0

º

C)

100.0ºF

(55.5

º

C)

Setpoint Screen #50 - CO

2

Sensor Calibration

- Current and Offset

VCC-X Spts ID:#

CO2 Sensor Cal

Current: 0ppm
Offset.: 0ppm

If the CO

2

Sensor is reading incorrectly, you can use this option

to enter an offset reading to adjust the Sensor’s Sensitivity. Line 3
will display the current CO

2

Sensor reading. Enter a positive Sensor

Calibration value in Line 4 to increase the CO

2

Sensor reading or a

negative value in Line 4 to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration

CO

2

-500.0 PPM

0.0 PPM

500.0 PPM

VCC-X Setpoint Screens