MODULAR SERVICE TOOL SD

14

VCC-X Operator Interface SD

The screens will step through the Start Time and then the Stop Time
for each day of the week. You can quit at any point in the process by
pressing

. There are two Start/Stop events available per day,

so the screen will show which event is being programmed. If you
need only one event, keep Event #2’s times set at ZERO.

All times are in 24-hour military format, so 5:00 PM would be
entered as 1700.

If both the Start and Stop Times are ZERO, the schedule is in a
continuous OFF mode. (Also, use for Remote Forced Occupied
applications using the Forced Occupied Binary Input.)

If both the Start and Stop Times are 2359, the schedule is in a con-
tinuous ON mode.

NOTE: The second line displays which day of the week is

currently being programmed. The day of the week
automatically increments as you exit the Event #2
screen for the day and continue to the next day’s Event
#1 screen.

CAUTION: The controller ships with all schedules set to

zero so that the controller will not attempt to heat

or cool before you have confi gured the system.

Holiday Start/Stop Day Selection

VCC-X Schd ID #

Holiday # 1

Start Mon/Day: XXXX
[ July 4

th

= 704 ]

VCC-X Schd ID #

Holiday # 1

Stop Mon/Day: XXXX
[ July 5

th

= 705 ]

The screens will step through the fourteen possible holidays, one
period at a time. Line 2 shows which holiday is currently being
programmed. Since a holiday period can encompass more than one
day, you need to program the day the holiday starts and the day the
holiday ends. If your holiday only lasts one day, simply set both the
Start Day and the Stop Day to the same value. Remember to combine
the month and day into a single four-digit value.

EXAMPLE:

704 = July 4

th

(

NOTE:

Leading zero not

required)

1225

=

December

25

th

Scheduling

You can access the Unit Controller Scheduling Screens by pressing

. The Unit Selection Screen will be displayed.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter the Unit ID of the controller the Service Tool is connected to
and press

. Once communication is established, the *00*

message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

Press

the

<

>

button and then

press

to access the

scheduling function you wish to view.

VCC-X Schedule Menu
Schedule Override

Week Schedules
Holidays

Week Schedules

Event #1

VCC-X Schd ID #

Sunday Event #1

Start Time: XXXX
Stop Time: XXXX

Event #2

VCC-X Schd ID #

Sunday Event #2

Start Time: XXXX
Stop Time: XXXX

If you are using the internal scheduling capability of the Unit Con-
troller, set the schedule hours and holiday periods from the menu
shown above. You can also force the unit to operate continuously in
occupied or unoccupied mode by selecting the Schedule Override
menu item and entering the desired command.

If you are using an external contact closure to signal the occupied
mode, you must access the Week Schedule Screens and set all start
and stop times to zero to prevent the internal schedule from turning
the equipment on when you don’t want it to operate.

Schedules and Holidays