VAV/ZONE CONFIGURATION

VCC-X Operator Interface SD

71

VAV/Zone Confi guration Screens

Confi guration Screen #9 - Push-Button

Override

XX Box Cnfg IDXXXX

Push-Button Override

Group ID #: 1

During Unoccupied Mode, all zones with a corresponding Group
ID # will resume Occupied operation whenever any of the zones
in that group has its push-button depressed to initiate an override
condition. This allows you to group zones in various areas of the
building. For example, individual tenants with several offi ces could
restore occupied mode for just their zones and not affect other zones
in the building.

The default group ID number for all VAV/Zone Controllers is set at
the factory to 1. If you don’t want a specifi c zone(s) to be part of that
group, you must give each one a distinct Group ID number between
2 and 16. Setting a zone’s Group ID number to 0 will disable the
Space Sensor Override Button function.

If you don’t want a specifi c zone to be a part of any group, enter

<0>

for its Group ID #.

Confi guration Screen #10 - Dump Zone

XX Box Cnfg IDXXXX

Is This A Dump Zone

(No Actuator): NO

Use < Or > To Change

A “Dump Zone” is used when you want to control a duct heater
or baseboard heater independently. A VAV/Zone Controller board
with a relay expansion board is used for this purpose. No damper
or actuator is used. If you need to control an auxiliary heater, select
YES; otherwise, be sure it is set to NO.

Confi guration Screen #11 - HVAC Unit is on

Separate Loop

XX Box Cnfg IDXXXX

HVAC Unit is on

Separate Loop: NO

Use < Or > To Change

If this system has 1 HVAC unit controlling boxes on multiple loops
and the HVAC unit is on a different loop than this box, select YES;
otherwise, be sure it is set to NO.