Vcc-x status, Vcc-x status screens, Vcc-x operator interface sd – Orion System VCC-X Controller User Manual

Page 55: Status screens - general procedures

background image

VCC-X Operator Interface SD

VCC-X STATUS

55

VCC-X Status Screens

Status Screens - General Procedures

From any menu screen, press

. The Unit Selection Screen,

shown below,

will appear requesting that you enter the unit ID number.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter

the correct unit ID number of the Controller you want to view

and press

. Once communication is established, the *00*

message will go away. Then

press

<

>

. You will then see the Status

Selection Screen(s) below:

VCC-X Status
RSM #1
RSM #2
Select & Press Enter

RSM #3
RSM #4

Select & Press Enter

Select VCC-X Status. Then press

.

The fi rst Status Screen will appear. Press

<

>

to scroll through

the screens.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

Status Screen #1 - Date and Time

VCC-X v1.02 ID #
Controller Date/Time

01/16/2015 05:00 PM

Line 2 Controller Date/Time

Line 3 MM/DD/YYYY HH:MM XX

(Month, Day, Year) (Hour, Minutes, AM or PM)

Status Screen #2 - Application Type, Schedule

Mode & HVAC Mode

VCC-X v1.02 ID #

App Type

Schedule Mode

HVAC Mode

Line 2 App Type:

Constant

Volume

Single

Zone

VAV

VAV

VAV

w/Tempering

Make Up Air Space w/High OA%


Line 3 Schedule Mode:

Unoccupied Holiday Occupied

Occupied

Forced

Occupied

Override

Forced

Unoccupied

Holiday

Unoccupied

Remote

Occupied

Line 4 HVAC Mode:

Off

Dehum

Vent

Vent

Mode

Dehum

Cool

Cool

Mode

Dehum

Heat

Heat

Mode

Warm

Up

Defrost

Cool

Down

Remote

Cool

Remote

Heat

Remote Vent RH Remote Cool RH

Remote

Heat

RH

Status Screen #3 - Controlling Temperature,

Cooling & Heating Setpoints

VCC-X v1.02 ID #

Ctrl Temp: 000.0ºF
Cool Spt: 000.0ºF
Heat Spt: 00.0ºF

Line 2 Controlling Temperature

This is the temperature of the sensor that is confi gured as

the HVAC Source (Mode Enable) Sensor. This can be

the Supply Air, Return Air, Outdoor Air, or Space

Temperature

Sensor.

Line 3 Cooling Setpoint

Based on the current Occupied/Unoccupied Mode

of

operation.

(Refl ects any active resets.)

Line 4 Heating Setpoint

Based on the current Occupied/Unoccupied Mode

of operation. (Refl ects any active resets.)