VCC-X CONFIGURATION

VCC-X Operator Interface SD

36

VCC-X Confi guration Screens

Confi guration Screen #62 - Broadcast to Boxes

VCC-X Cnfg ID #

Broadcast to Boxes

NO

USE < or > TO CHANGE

The VCC-X can broadcast all applicable information and commands
to the VAV Boxes. Select YES for Broadcast to Boxes. Default is NO.

Confi guration Screen #63- #66 - Cool/Heat

Stage Delays

VCC-X Cnfg ID #

Cool Stage Delays
Stage Up: 3 Min
Stage Down: 1 Min

VCC-X Cnfg ID #

Cool Stage Delays

Min Run: 5 Min
Min Off: 3 Min

VCC-X Cnfg ID #

Heat Stage Delays

Stage Up: 3 Min
Stage Down: 1 Min

VCC-X Cnfg ID #

Heat Stage Delays

Min Run: 5 Min
Min Off: 1 Min

Both the Heating Stages and the DX Cooling Stages utilize Staging
Up
and Down Delay Periods between stages and Minimum Run
Times and Off Times.

See the VCC-X Controller Technical Guide for information on how
these Delays and Run Times are used.

Description

Minimum

Default

Maximum

Cooling Stage Up

3 Min

3 Min

15 Min

Cooling Stage Down

1 Min

1 Min

15 Min

Cooling Min Run Time

5 Min

5 Min

15 Min

Cooling Min Off Time

3 Min

3 Min

15 Min

Heating Stage Up

3 Min

3 Min

15 Min

Heating Stage Down

1 Min

1 Min

15 Min

Heating Min Run Time

2 Min

5 Min

15 Min

Heating Min Off Time

1 Min

1 Min

15 Min

Confi guration Screen #67 - Heat/Cool

Changeover Delay

VCC-X Cnfg ID #

Heat Cool Changeover

Delay: 5Min

[ 0 - 20 Minutes ]

Enter

the time in minutes for the time delay when the unit changes

over from a call to heating to a call to cooling and vice versa. De-
fault is 5 minutes.

Confi guration Screen #68 - Return Air Bypass

Control

VCC-X Cnfg ID #

Return Air Bypass

Control: NO

USE < or > TO CHANGE

Select Yes if your HVAC unit requires Return Air Bypass Control for
Dehumidifi cation Reheat. Default is NO. You must have the EM1
Expansion Module installed and confi gured for this feature.

Confi guration Screen #69 - Morning

Cool-Down Type

VCC-X Cnfg ID #

Morning Cool-Down

None

USE < or > TO CHANGE

You can choose between the following Morning Cool-Down options.
Default is None. Available options are:

None

—There is no Cool-Down required.

Stand Alone

The VCC-X Controller is not

communicating to Orion VAV Box controls, but a

Cool-Down Relay can be confi gured to signal boxes by

others to open.

Bcast Fixed to Boxes

—The VCC-X Controller is

communicating to Orion VAV Boxes and will broadcast

a command to the boxes to go to a Fixed Percentage

Position

or

Airfl ow while in Cool-Down. This fi xed

position is confi gured in the VAV Box Controller.

Bcast Max to Boxes

—The VCC-X Controller is

communicating to Orion VAV Boxes and will broadcast

a command to the boxes to go to a Maximum Percentage

Position

or

Airfl ow while in Cool-Down. This maximum

position is confi gured in the VAV Box Controller.