VCC-X SETPOINTS

VCC-X Operator Interface SD

52

Setpoint Screen #46 - Space Sensor

Calibration - Current and Offset

VCC-X Spts ID:#

Space Sensor Cal

Current: 0.0ºF
Offset.: 0.0ºF

If the Space Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Space Air Temperature
reading. Enter a positive Sensor Calibration value in Line 4 to raise
the Space Temperature Sensor reading or a negative value in Line
4 to lower the Sensor reading.

Description

Minimum

Default

Maximum

Space Sensor
Calibration Offset

-100.0ºF

(-55.5

º

C)

0.0ºF
(0

º

C)

100.0ºF

(55.5

º

C)

Setpoint Screen #47 - Return Air Temperature

Sensor Calibration - Current and Offset

VCC-X Spts ID:#

Return Sensor Cal

Current: 0.0ºF
Offset.: 0.0ºF

If the Return Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Return Air Temperature
reading. Enter a positive Sensor Calibration value in Line 4 to raise
the Return Temperature Sensor reading or a negative value in Line
4 to lower the Sensor reading.

Description

Minimum

Default

Maximum

Return Air Sensor
Calibration Offset

-100.0ºF

(-55.5

º

C)

0.0ºF
(0

º

C)

100.0ºF

(55.5

º

C)

Setpoint Screen #48 - SAT Sensor Calibration

- Current and Offset

VCC-X Spts ID:#

SAT Sensor Cal

Current: 0.0ºF
Offset.: 0.0ºF

If the Supply Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Supply Air Temperature
Sensor reading. Enter a positive Sensor Calibration value in Line
4 to raise the Supply Air Temperature Sensor reading or a negative
value in Line 4 to lower the Sensor reading.

Description

Minimum

Default

Maximum

Sensor Calibration SAT

-100.0ºF

(-55.5

º

C)

0.0ºF
(0

º

C)

100.0ºF

(55.5

º

C)

VCC-X Setpoint Screens